YASKAWA HV600 Manual page 395

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

n7-08: Speed Calculation Gain2
No.
Name
(Hex.)
n7-08
Speed Calculation Gain2
(3118)
Expert
Note:
• When E9-01 = 1 [Motor Type Selection = Permanent Magnet (PM)], the default setting is 0 Hz and the setting range is 1.0 - 80.0 Hz.
• When you increase the setting value, you can do a speed search of a motor rotating at a high frequency. If the setting value is too high, the
calculated speed will oscillate and a restart will fail. Decrease the setting value in these conditions.
n7-10: Pull-in Current Switching Speed
No.
Name
(Hex.)
n7-10
Pull-in Current Switching
Speed
(311A)
Expert
Note:
• The value set in n8-51 [Pull-in Current @ Acceleration is enabled for speeds that are not higher than n7-10 during deceleration. The value
set in b8-01 [Energy Saving Control Selection] is enabled for speeds higher than n7-10.
• If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.
• When it is most important to save energy in the low speed range, decrease the setting value.
n7-11: Pull-in Current Switch Hysteresis Band
No.
Name
(Hex.)
n7-11
Pull-in Current Switch
Hysteresis Band
(311B)
Expert
Note:
• The value set in n8-51 [Pull-in Current @ Acceleration] is enabled for speeds that are not higher than n7-10 + n7-11 during acceleration.
The value set in b8-01 [Energy Saving Control Selection] is enabled for speeds higher than n7-10 + n7-11.
• If there is a large quantity of oscillation when you operate in the low speed range, increase the setting value.
• When it is most important to save energy in the low speed range, decrease the setting value.
n7-13: Pull-in Current Switching Time
No.
Name
(Hex.)
n7-13
Pull-in Current Switching
Time
(311D)
Expert
If there is a large quantity of oscillation at speeds around n7-10 [Pull-in Current Switching Speed], decrease the
setting in decrements of 20 ms.
n7-17: Resistance TemperatureCorrection
No.
Name
(Hex.)
n7-17
Resistance
TemperatureCorrection
(3122)
0 : Invalid
1 : Valid (Only 1 time)
2 : Valid (Every time)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
Sets the speed calculation gain during a speed search.
V/f
OLV/PM
OLV/PM EZOLV
Parameter n8-51 [Pull-in Current @ Acceleration], is in effect when the output frequency is ≤ n7-10,
where the speed is set as a percentage of rated speed.
V/f
OLV/PM
OLV/PM EZOLV
Sets the hysteresis level for Switching Speed set in n7-10 [Pull-in Current Switching Speed]. When
the speed is lower than n7-10 + n7-11 during acceleration, the drive enables pull-in current.
V/f
OLV/PM EZOLV
OLV/PM
Sets a time to enable the pull-in current commands.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to adjust for changes in the motor resistance value caused by changes in the
temperature.
Description
Description
Description
Description
Description
2.10 n: Special Adjustment
Default
(Range)
25.0 Hz
(1.0 - 50.0 Hz)
Default
(Range)
10.0%
(0.0 - 100.0%)
Default
(Range)
5.0%
(1.0 - 20.0%)
Default
(Range)
100 ms
(0 - 1000 ms)
Default
(Range)
1
(0 to 2)
2
395

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF