0 : No Retry
1 : Retry
L5-51: Loss of Prime Fault Retry Select
No.
Name
(Hex.)
L5-51
Loss of Prime Fault Retry
Select
(367B)
0 : No Retry
1 : Retry
L5-53: Thermostat Fault Retry Selection
No.
Name
(Hex.)
L5-53
Thermostat Fault Retry
Selection
(3251)
Note:
• To use this function, set S5-01 ≠ 0 [HAND Frequency Reference Source ≠ HAND Analog Input]
• The drive will only restart after the Thermostat digital input deactivates and the L5-04 [Interval Method Restart Time] timer is expired.
0 : No Retry
1 : Retry
Figure 2.101
shows the drive operation for VLTS when L5-53 = 1 and L5-01 [Number of Auto-Restart Attempts] > 0
times. The drive will wait for the Thermostat digital input to deactivate + the L5-04 time before it will restart.
H1-xx = 188:
H2-xx = 95:

L6: Torque Detection

The overtorque/undertorque/underload detection function prevents damage to machinery and loads.
Overtorque is when there is too much load on the machine. If the motor current or output torque is at the overtorque
detection level for the overtorque detection time, the drive will output an alarm and turn off the output.
Undertorque and underload are when a load suddenly decreases. When the motor current or output torque is at the
undertorque/underload detection level for the undertorque detection time, the drive will output an alarm and turn off
the output.
You can use the undertorque/underload detection function to detect these conditions, for example:
• Machine belt breaks
• Unusual operation of the electromagnetic contactor on the drive output side
• Clogged output side air filters in fans and blowers
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive to try an Auto Restart if it detects an LOP [Loss Of Prime] fault.
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive to try an Auto Restart if it detects a VLTS [Thermostat Fault] fault.
Figure 2.101 Thermostat Fault Behavior
Description
Description
L5-04:
VLTS Fault:
2.9 L: Protection Functions
Default
(Range)
0
(0, 1)
Default
(Range)
1
(0, 1)
2
375