4.6 Control I/O Connections
4.6
Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
• MFDI (terminals S1 to S7)
• MFDO (terminals M1 to M6)
• MFAI (terminals A1, A2)
• MFAO (terminals FM, AM)
• RS-485 communications (terminals D+, D-, AC)
◆
Set Sinking Mode/Sourcing Mode
Close the circuit between terminals SC-SP and SC-SN to set the sinking mode/sourcing mode and the internal/
external power supply for the MFDI terminals. The default setting for the drive is internal power supply sinking
mode.
NOTICE: Damage to Equipment. Do not close the circuit between terminals SP-SN. If you close the circuits between terminals SC-
SP and terminals SC-SN at the same time, it will cause damage to the drive.
Mode
Sinking Mode (NPN)
Sourcing Mode
(PNP)
◆
Set Input Signals for MFAI Terminals A1 and A2
Use terminals A1 and A2 to input a voltage or a current signal. Set the signal type as shown in
598
Internal Power Supply (Terminal SN-SP)
Figure 4.31 Location of Jumper Switch S1
External 24 V Power Supply
Table
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
4.12.