YASKAWA HV600 Manual page 183

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

When reverse operation is prohibited, the drive will not accept a Reverse operation command.
0 : Reverse Enabled
The drive will accept a Reverse operation command.
1 : Reverse Disabled
The drive will not accept a Reverse operation command.
b1-08: Run Command Select in PRG Mode
No.
Name
(Hex.)
b1-08
Run Command Select in
PRG Mode
(0187)
As a safety precaution, when the drive is in Programming Mode, it will not respond to a Run command.
This parameter helps prevent accidents that can occur if the motor starts to rotate because the drive received a Run
command from an external source while the user is programming the drive. You can also set the drive to not show the
Programming Mode when a Run command is active.
Note:
Refer to this table for Drive Mode and Programming Mode functions.
Mode
Drive Mode
Monitors
Parameters
User Custom Parameters
Parameter Backup/Restore
Programming Mode
Modified Parameters/Fault Log
Auto-Tuning
Initial Setup
Diagnostic Tools
0 : Disregard RUN while Programming
The drive rejects the Run command while in Programming Mode.
1 : Accept RUN while Programming
The drive accepts a Run command entered from an external source while in Programming Mode.
2 : Allow Programming Only at Stop
The drive does not let the user enter Programming Mode when the drive is operating. The drive does not show the
Programming Mode when a Run command is active.
b1-11: Run Delay @ Stop
No.
Name
(Hex.)
b1-11
Run Delay @ Stop
(01DF)
Note:
• This parameter will operate for both AUTO Mode and HAND Mode.
• This parameter will operate when the drive goes to sleep then wakes up.
• The time set in this parameter does not apply for faults or Auto-Restarts.
• When there is an active Run command while the time set in b1-11 is active, the keypad will show a [Start Delay] message as specified by
the o1-82 [Message Screen Display] display format.
Coast to Stop with Timer Function
When b1-03 = 3 [Stopping Method Selection = Coast to Stop with Timer], the drive operates as:
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the conditions for the drive to accept a Run command entered from an external source when
using the keypad to set parameters.
Keypad Screen
Sets monitor display.
Changes parameter settings.
Shows the User Parameters.
Saves parameters to the keypad as backup.
Shows modified parameters and fault history.
Auto-Tunes the drive.
Changes initial settings.
Sets data logs and backlight.
V/f
OLV/PM
OLV/PM EZOLV
Sets the amount of time that the drive will not accept the Run command again after the Run
command is lost.
Description
Function
Description
2.3 b: Application
Default
(Range)
0
(0 - 2)
Default
(Range)
0.0 s
(0.0 - 6000.0 s)