YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when you input a Run command and when the drive is outputting voltage.
ON : Drive is stopping
OFF : Drive is running
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the output frequency < E1-09 [Minimum Output Frequency].
Note:
Parameter E1-09 is the reference in all control methods.
ON : Output frequency ≥ value of E1-09.
OFF : Output frequency < value of E1-09.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree
Detection Width].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency does not align with the frequency reference although the drive is running.
OFF : The output frequency is in the range of "frequency reference ± L4-02".
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02
[Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency is not in the range of "L4-01 ± L4-02" or the range of frequency reference ± L4-02.
OFF : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ± L4-02.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the output frequency > "L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree
Detection Width]". After the terminal activates, the terminal stays activated until the output frequency is at the value of
L4-01.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency > "L4-01 + L4-02".
OFF : The output frequency < L4-01, or the output frequency ≤ "L4-01 + L4-02"
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the output frequency > L4-01 [Speed Agree Detection Level]. After the terminal
deactivates, the terminal stays deactivated until the output frequency is at the value of "L4-01 - L4-02 [Speed Agree
Detection Width]".
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency < "L4-01 - L4-02", or the output frequency ≤ L4-01
OFF : The output frequency > L4-01
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive is ready and running.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the DC bus voltage or control circuit power supply is at the voltage set in L2-05
[Undervoltage Detection Lvl (Uv1)] or less. The terminal also deactivates when there is a fault with the DC bus
voltage.
ON : The DC bus voltage > L2-05
OFF : The DC bus voltage ≤ L2-05
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock.
V/f
OLV/PM EZOLV
OLV/PM
Shows the selected frequency reference source.
ON : Parameter b1-01 [Frequency Reference Selection 1] is the frequency reference source.
OFF : The keypad is the frequency reference source.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque > L6-02 [Torque Detection Level 1], or < L6-02 for longer than the time set with L6-
03 [Torque Detection Time 1].
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects a loss of frequency reference.
1.10 H: Terminal Functions
Description
Ref.
324
324
324
324
324
324
324
324
324
324
1
324
324
65