L4: Speed Detection - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.9 L: Protection Functions
L3-26: Additional DC Bus Capacitors
No.
Name
(Hex.)
L3-26
Additional DC Bus
Capacitors
(0455)
Expert
L3-27: Stall Prevention Detection Time
No.
Name
(Hex.)
L3-27
Stall Prevention Detection
Time
(0456)
L3-35: Speed Agree Width for Auto Decel
No.
Name
(Hex.)
L3-35
Speed Agree Width for Auto
Decel
(0747)
Expert
Set this parameter when hunting occurs while you use a frequency reference through an analog input.

L4: Speed Detection

L4 parameters set the output of signals to the MFDO terminals, for example frequency agree and frequency detection.
L4-01: Speed Agree Detection Level
No.
Name
(Hex.)
L4-01
Speed Agree Detection
Level
(0499)
L4-02: Speed Agree Detection Width
No.
Name
(Hex.)
L4-02
Speed Agree Detection
Width
(049A)
L4-03: Speed Agree Detection Level (+/-)
No.
Name
(Hex.)
L4-03
Speed Agree Detection
Level (+/-)
(049B)
L4-04: Speed Agree Detection Width (+/-)
No.
Name
(Hex.)
L4-04
Speed Agree Detection
Width (+/-)
(049C)
368
V/f
OLV/PM
OLV/PM EZOLV
Sets the capacity for external main circuit capacitors. Usually it is not necessary to change this
setting. Sets this parameter when you use the KEB Ride-Thru function.
V/f
OLV/PM EZOLV
OLV/PM
Sets a delay time between reaching the Stall Prevention level and starting the Stall Prevention
function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the width for speed agreement when L3-04 = 2 [Decel Stall Prevention Selection = Automatic
Decel Reduction]. Usually it is not necessary to change this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the level to detect speed agree or motor speed when H2-01 to H2-03 = 2, 3, 4, 5 [MFDO
Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency
Detection 2].
V/f
OLV/PM
OLV/PM EZOLV
Sets the width to detect speed agree or motor speed when H2-01 to H2-03 = 2, 3, 4, 5 [MFDO
Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency Detection 1, Frequency
Detection 2].
V/f
OLV/PM
OLV/PM EZOLV
Sets the speed agree detection level or motor speed detection level when H2-01 to H2-03 = 13, 14,
15, 16 [MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3,
Frequency Detection 4].
V/f
OLV/PM EZOLV
OLV/PM
Sets the width to detect speed agree or motor speed when H2-01 to H2-03 = 13, 14, 15, 16 [MFDO
Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency Detection 3, Frequency
Detection 4].
Description
Description
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0 μF
(0 to 65000 μF)
Default
(Range)
50 ms
(0 - 5000 ms)
Default
(Range)
0.00 Hz
(0.00 - 1.00 Hz)
Default
(Range)
0.0 Hz
(0.0 - 400.0 Hz)
Default
(Range)
2.0 Hz
(0.0 - 20.0 Hz)
Default
(Range)
0.0 Hz
(-400.0 - +400.0 Hz)
Default
(Range)
2.0 Hz
(0.0 - 20.0 Hz)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents