1.10 H: Terminal Functions
No.
Name
(Hex.)
H5-03
Communication Parity
Selection
(0427)
H5-04
Communication Error
Stop Method
(0428)
H5-05
Comm Fault Detection
Selection
(0429)
H5-06
Drive Transmit Wait
Time
(042A)
H5-08
Communication Protocol
Selection
(062D)
H5-09
CE Detection Time
(0435)
H5-10
Modbus Register 0025H
Unit Sel
(0436)
H5-11
Comm ENTER
Command Mode
(043C)
H5-12
Run Command Method
Selection
(043D)
H5-14
BACnet Device Obj ID
LOW BITS
(310D)
H5-15
BACnet Device Obj ID
HIGH BITS
(310E)
H5-18
Motor Speed Filter over
Comms
(11A2)
H5-20
Communication
Parameters Reload
(0B57)
74
V/f
OLV/PM EZOLV
OLV/PM
Sets the communications parity used for MEMOBUS/Modbus communications.
Note:
Re-energize the drive or set H5-20 = 1 [Communication Parameters Reload = Reload
Now] after you change the parameter setting.
0 : No parity
1 : Even parity
2 : Odd parity
V/f
OLV/PM
OLV/PM EZOLV
Sets the motor Stopping Method when the drive detects a Modbus Communication Error
condition.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : Run at H5-34 (CE Go-To-Freq)
V/f
OLV/PM EZOLV
OLV/PM
Sets the function that detects CE [Modbus Communication Error] issues during
MEMOBUS/Modbus communications.
0 : Disabled
1 : Enabled
V/f
OLV/PM
OLV/PM EZOLV
Sets the time to wait to send a response message after the drive receives a command
message from the master.
Note:
Restart the drive after changing the parameter setting.
V/f
OLV/PM EZOLV
OLV/PM
Selects the communication protocol.
0 : Modbus/MEMOBUS
1 : Metasys/N2
2 : Apogee/P1
3 : BACnet
V/f
OLV/PM
OLV/PM EZOLV
Sets the detection time for CE [Modbus Communication Error] issues when
communication stops.
V/f
OLV/PM EZOLV
OLV/PM
Sets the unit of measure used for the MEMOBUS/Modbus communications monitor
register 0025H (output voltage reference monitor).
0 : 0.1 V units
1 : 1 V units
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to make the Enter command necessary to change parameters through
MEMOBUS/Modbus communications.
0 : ENTER Command Required
1 : ENTER Command Not Required
V/f
OLV/PM
OLV/PM EZOLV
Sets the input method for the Run command when b1-02 = 2 [Run Command Selection 1 =
Serial Communications].
0 : FWD/Stop, REV/Stop
1 : Run/Stop, FWD/REV
V/f
OLV/PM EZOLV
OLV/PM
Sets the lower bits of the BACnet device object ID as a 4-digit hexadecimal number.
V/f
OLV/PM
OLV/PM EZOLV
Sets the upper bits of the BACnet device object ID as a 4-digit hexadecimal number.
V/f
OLV/PM EZOLV
OLV/PM
Sets the filter time constant used when monitoring motor speed during MEMOBUS/
Modbus communications or with a communication option.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to immediately enable updated MEMOBUS/Modbus communications
parameters.
0 : Reload at Next Power Cycle
1 : Reload Now
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
Ref.
(Range)
0
340
(0 - 2)
3
340
(0 - 4)
1
341
(0, 1)
5 ms
341
(0 - 65 ms)
0
342
(0 - 3)
2.0 s
342
(0.0 - 10.0 s)
0
342
(0, 1)
0
342
(0, 1)
0
342
(0, 1)
0001
343
(0000 - FFFF)
0000
343
(0000 - 003F)
0 ms
343
(0 - 100 ms)
0
344
(0, 1)

Hide quick links: