T4: Ez Tuning - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
T2-03
PM Motor Type
(0752)
T2-04
PM Motor Rated Power
(0730)
T2-05
PM Motor Rated Voltage
(0732)
T2-06
PM Motor Rated Current
(0733)
T2-07
PM Motor Base
Frequency
(0753)
T2-08
Number of PM Motor
Poles
(0734)
T2-10
PM Motor Stator
Resistance
(0754)
T2-11
PM Motor d-Axis
Inductance
(0735)
T2-12
PM Motor q-Axis
Inductance
(0736)
T2-13
Back-EMF Units
Selection
(0755)
T2-14
Back-EMF Voltage
Constant (Ke)
(0737)
T2-15
Pull-In Current Level
(0756)

T4: EZ Tuning

No.
Name
(Hex.)
T4-01
EZ Tuning Mode
Selection
(3130)
T4-02
Motor Type Selection
(3131)
T4-03
Motor Max Revolutions
(3132)
T4-04
Motor Rated Revolutions
(3133)
T4-05
Motor Rated Frequency
(3134)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the type of PM motor the drive will operate.
0 : IPM motor
1 : SPM motor
V/f
OLV/PM
OLV/PM EZOLV
Uses the units set in o1-58 [Motor Power Unit Selection] to set the PM motor rated output
power.
V/f
OLV/PM
OLV/PM EZOLV
Sets the rated voltage (V) of the motor.
V/f
OLV/PM
OLV/PM EZOLV
Sets the rated current (A) of the motor.
V/f
OLV/PM
OLV/PM EZOLV
Sets the base frequency (Hz) of the motor.
V/f
OLV/PM
OLV/PM EZOLV
Sets the number of motor poles.
V/f
OLV/PM
OLV/PM EZOLV
Sets the stator resistance for each motor phase.
Note:
This parameter does not set line-to-line resistance.
V/f
OLV/PM
OLV/PM EZOLV
Sets the d-axis inductance of the motor on a per phase basis.
V/f
OLV/PM EZOLV
OLV/PM
Sets the q-Axis inductance of the motor on a per phase basis.
V/f
OLV/PM
OLV/PM EZOLV
Sets the units that the drive uses to set the induced voltage constant.
0 : mV/(rev/min)
1 : mV/(rad/sec)
V/f
OLV/PM EZOLV
OLV/PM
Sets the motor induced voltage constant (Ke).
V/f
OLV/PM EZOLV
OLV/PM
Sets the level of the pull-in current as a percentage of E5-03 [PM Motor Rated Current
(FLA)]. Usually it is not necessary to change this setting.
Description
V/f
OLV/PM EZOLV
OLV/PM
Sets the type of Auto-Tuning for EZOLV control.
0 : Motor Parameter Setting
1 : Line-to-Line Resistance
V/f
OLV/PM
OLV/PM EZOLV
Sets the type of motor.
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
V/f
OLV/PM EZOLV
OLV/PM
Sets the maximum motor revolutions (min
V/f
OLV/PM EZOLV
OLV/PM
Sets rated rotation speed (min
-1
) of the motor.
V/f
OLV/PM EZOLV
OLV/PM
Sets the rated frequency (Hz) of the motor.
-1
).
1.17 T: Motor Tuning
Default
Ref.
(Range)
1
462
(0, 1)
Determined by o2-04
463
(0.00 - 650.00 HP)
208 V Class: 230.0 V,
463
480 V Class: 460.0 V
(208 V Class: 0.0 - 255.0
V,
480 V Class: 0.0 - 510.0
V)
Determined by o2-04
463
(10% to 200% of the
drive rated current)
60.0 Hz
463
(0.0 - 400.0 Hz)
4
463
(2 - 48)
Determined by T2-02
463
(0.000 - 65.000 Ω)
Determined by T2-02
463
(0.00 - 600.00 mH)
Determined by T2-02
464
(0.00 - 600.00 mH)
0
464
(0, 1)
Determined by T2-13
464
(0.0 - 2000.0)
30%
464
(0 - 120%)
Default
Ref.
(Range)
0
465
(0, 1)
0
465
(0, 1, 2)
-
465
((40 to 120 Hz) × 60 × 2 /
E9-08)
-
465
((40 Hz to 120 Hz) × 60 ×
2/E9-08)
Determined by E9-01 and
465
o2-04
(40.0 - 120.0 Hz)
111
1

Hide quick links:

Advertisement

Table of Contents
loading