2.11 o: Keypad-Related Settings
Unit Code (Hex.)
Unit
02
RPM
03
%
04
VAC
05
VDC
06
A
07
sec
Third and Subsequent Rows: Log Data
This example shows the data text strings and data generated for the third row of log data.
Example of generated data:
02,0012,160107111239,1770,1770,00BE,0118,0028,0000,0000,0000,0000,0000,0000,0000,00000C
No.
Item
1
Attribute
2
File number
3
Time stamp
4
Log Monitor Data 1
5
Log Monitor Data 2
:
:
13
Log Monitor Data 10
14
Reserved
15
Encoding data
16
File number
o5-01: Log Start/Stop Selection
No.
Name
(Hex.)
o5-01
Log Start/Stop Selection
(1551)
RUN
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
o5-02: Log Sampling Interval
No.
Name
(Hex.)
o5-02
Log Sampling Interval
(1552)
RUN
426
Unit Code (Hex.)
Unit
0A
Ω
0B
ms
0C
kHz
0D
PSI
0E
MPM
0F
FPM
Number of
Characters
2
[02] shows that the record is a monitor data record.
4
The [xxx] part of the [GLOG0xxx.csv] filename is a 3-digit decimal number in hexadecimal format.
12
Data log data was retrieved (YYMMDDHHMMSS)
4
Monitor number selected by o5-03 [Log Monitor Data 1]
4
Monitor number selected by o5-04 [Log Monitor Data 2]
:
:
4
Monitor number selected by o5-12 [Log Monitor Data 10]
4
-
4
Encoding data for log monitor data 1 to 10 (Hex.)
Bits 0 to 9 show the encoding of log monitor data 1 to 10. A bit value of 1 shows that the data represents a negative value.
(Log monitor data 1 to 10 are absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have values of 1, and the encoding data
= 0010010010 (Bin.) = 0092 (Hex.)
6
Row number (Hex.) in the data log file
V/f
OLV/PM
OLV/PM EZOLV
Sets the data log function. This parameter is only available on an HOA keypad.
V/f
OLV/PM
OLV/PM EZOLV
Sets the data log sampling cycle. This parameter is only available on an HOA keypad.
Unit Code (Hex.)
Unit
12
us
13
min
14
°C
15
W
16
kWH
17
MWH
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Unit Code (Hex.)
Unit
1A
1B
1C
1D
1E
1F
Default
(Range)
0
(0 - 1)
Default
(Range)
100 ms
(100 - 60000 ms)

Hide quick links: