2.10 n: Special Adjustment
Note:
• For settings 1 and 2, the adjustment time can cause a delay before startup.
• For settings 1 and 2, the drive can set the line-to-line resistance value of E9-10 [Motor Line-to-Line Resistance].
• When the temperature will change at startup, use setting 2.
• To decrease the startup time, set this parameter to 0, then do line-to-line resistance tuning.
• If you will start from coasting, set this parameter to 0, then do line-to-line resistance tuning.

n8: PM Motor Control Tuning

n8 parameters are used to make adjustments when controlling PM motors.
n8-23: ACR q Gain @PoleEst
No.
Name
(Hex.)
n8-23
ACR q Gain @PoleEst
(0556)
Expert
n8-24: ACR q Integral Time @PoleEst
No.
Name
(Hex.)
n8-24
ACR q Integral Time
@PoleEst
(0557)
Expert
n8-25: ACR q Limit @PoleEst
No.
Name
(Hex.)
n8-25
ACR q Limit @PoleEst
(0558)
Expert
n8-26: ACR d Gain @PoleEst
No.
Name
(Hex.)
n8-26
ACR d Gain @PoleEst
(0559)
Expert
n8-27: ACR d Integral Time @PoleEst
No.
Name
(Hex.)
n8-27
ACR d Integral Time
@PoleEst
(055A)
Expert
n8-28: ACR d Lim @PoleEst
No.
Name
(Hex.)
n8-28
ACR d Lim @PoleEst
(055B)
Expert
396
V/f
OLV/PM
OLV/PM EZOLV
Sets the proportional gain for current regulator q-axis control when the drive estimates the initial
pole. Usually it is not necessary to change this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the integral time for current regulator q-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the q-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the proportional gain for current regulator d-axis control when the drive estimates the initial
pole. Usually it is not necessary to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the integral time for current regulator d-axis control when the drive estimates the initial pole.
Usually it is not necessary to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the d-axis limit of the current regulator when the drive estimates the initial pole. Usually it is not
necessary to change this setting.
Description
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0
(0 - 2000)
Default
(Range)
0.0 ms
(0.0 - 100.0 ms)
Default
(Range)
0%
(0 - 150%)
Default
(Range)
500
(0 - 2000)
Default
(Range)
0.0 ms
(0.0 - 100.0 ms)
Default
(Range)
100%
(0 - 150%)