YASKAWA HV600 Manual page 126

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

1.18 U: Monitors
No.
Name
(Hex.)
U6-04
ASR Output
(0055)
U6-05
OutputVoltageRef: Vq
(0059)
U6-06
OutputVoltageRef: Vd
(005A)
U6-10
ContAxisDeviation Δθ
(07C1)
Expert
U6-14
MagPolePosition(Obs)
(07CB)
Expert
U6-17
Energy Save Coeff
(07D1)
Expert
U6-21
Offset Frequency
(07D5)
U6-31
TorqueDetect Monitor
(007B)
U6-36
Comm Errors-Host
(0720)
Expert
U6-37
Comm Errors-Host
(0721)
Expert
U6-57
PolePolarityDeterVal
(07C4)
U6-80
Option IP Address 1
(07B0)
U6-81
Option IP Address 2
(07B1)
U6-82
Option IP Address 3
(07B2)
U6-83
Option IP Address 4
(07B3)
U6-84
Online Subnet 1
(07B4)
U6-85
Online Subnet 2
(07B5)
U6-86
Online Subnet 3
(07B6)
U6-87
Online Subnet 4
(07B7)
126
V/f
OLV/PM
OLV/PM EZOLV
Shows the ASR output value as a percentage of the motor rated secondary current.
Unit: 0.01%
V/f
OLV/PM
OLV/PM EZOLV
Shows the drive internal voltage reference for motor secondary current control (q-Axis).
Unit: 0.1 V
V/f
OLV/PM EZOLV
OLV/PM
Shows the drive internal voltage reference for motor excitation current control (d-Axis).
Unit: 0.1 V
V/f
OLV/PM EZOLV
OLV/PM
Shows the deviation between the γδ-Axis that the drive uses for motor control and the dq-Axis.
Unit: 0.1 °
V/f
OLV/PM
OLV/PM EZOLV
Shows the value of the flux position estimation.
Unit: 0.1 °
V/f
OLV/PM EZOLV
OLV/PM
Shows the total time of direction of motor rotation detections for Speed Estimation Speed Searches.
This value adjusts b3-26 [Direction Determination Level].
Note:
Upper limit is +32767 and lower limit is -32767.
V/f
OLV/PM EZOLV
OLV/PM
Shows the total value of d7-01 to d7-03 [Offset Frequency 1 to 3] selected with Add Offset
Frequency 1 to 3 [H1-xx = 44 to 46].
Unit: 0.1%
V/f
OLV/PM EZOLV
OLV/PM
Monitors the torque reference or the output current after applying the filter.
Unit: 0.1%
V/f
OLV/PM
OLV/PM EZOLV
Shows the number of inter-CPU communication errors. When you de-energize the drive, this value
resets to 0.
V/f
OLV/PM
OLV/PM EZOLV
Shows the number of inter-CPU communication errors. When you de-energize the drive, this value
resets to 0.
V/f
OLV/PM EZOLV
OLV/PM
Shows the change from the integrated current when the drive finds the polarity.
Unit: 1
Note:
If the change from the integrated current is less than 819, increase n8-84 [Polarity Detection
Current]. U6-57 = 8192 is equivalent to the motor rated current.
V/f
OLV/PM EZOLV
OLV/PM
Shows the currently available local IP Address (1st octet).
V/f
OLV/PM EZOLV
OLV/PM
Shows the currently available local IP Address (2nd octet).
V/f
OLV/PM
OLV/PM EZOLV
Shows the currently available local IP Address (3rd octet).
V/f
OLV/PM
OLV/PM EZOLV
Shows the currently available local IP Address (4th octet).
V/f
OLV/PM
OLV/PM EZOLV
Shows the currently available subnet mask (1st octet).
V/f
OLV/PM EZOLV
OLV/PM
Shows the currently available subnet mask (2nd octet).
V/f
OLV/PM EZOLV
OLV/PM
Shows the currently available subnet mask (3rd octet).
V/f
OLV/PM EZOLV
OLV/PM
Shows the currently available subnet mask (4th octet).
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
MFAO Signal Level
10 V: Motor secondary rated
current (0 V to +10 V)
208 V class: 10 V = 200
Vrms
480 V class: 10 V = 400
Vrms
(-10 V to +10 V)
208 V class: 10 V = 200
Vrms
480 V class: 10 V = 400
Vrms
(-10 V to +10 V)
5 V: 180 ° (0 V to +10 V)
10 V: 180 ° (0 V to +10 V)
No signal output available
10 V: Maximum Frequency
10 V:100%
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available

Hide quick links: