2.7 F: Options
F7-23 to F7-32: Dynamic Out Param 1 to 10 for CommCard
No.
Name
(Hex.)
F7-23 to F7-27
Dynamic Out Param 1 to 10
for CommCard
(03FB - 03FF)
F7-28 to F7-32
(0370 - 0374)
F7-33 to F7-42: Dynamic In Param 1 to 10 for CommCard
No.
Name
(Hex.)
F7-33 to F7-42
Dynamic In Param 1 to 10
for CommCard
(0375 - 037E)
276
V/f
OLV/PM EZOLV
OLV/PM
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a ProfiNet option, set F7-23 to F7-27 to configurable Output 1-
5.
V/f
OLV/PM EZOLV
OLV/PM
When you use an Ethernet/IP option, sets Input Assembly 166. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set F7-33 to
F7-37 to configurable inputs 1-5.
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0
Default
(Range)
0