E1-09:
ON : Output frequency < E1-09.
OFF : Output frequency ≥ E1-09.
2: Speed Agree 1
Setting Value
Function
2
Speed Agree 1
Note:
The detection function operates in the two motor rotation directions.
L4-02:
ON : The output frequency is in the range of "frequency reference ± L4-02".
OFF : The output frequency does not align with the frequency reference although the drive is
running.
3: User-Set Speed Agree 1
Setting Value
Function
3
User-Set Speed Agree 1
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
ON : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ±
L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" or the range of frequency
reference ± L4-02.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Figure 2.60 Zero Speed Time Chart
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection Width].
Figure 2.61 Speed Agree 1 Time Chart
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree
Detection Width] and in the range of the frequency reference ± L4-02.
2.8 H: Terminal Functions
Description
Description
2
309