YASKAWA HV600 Manual page 321

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

72: High PI2 Control Feedback Level
Setting Value
Function
72
High PI2 Control Feedback
Level
89: Output Current Lim
Setting Value
Function
89
Output Current Lim
90 to 92: DWEZ Digital Outputs 1 to 3
Setting Value
Function
90 to 92
DWEZ Digital Outputs 1 to
3
94: Loss of Prime
Setting Value
Function
94
Loss of Prime
95: Thermostat Fault
Setting Value
Function
95
Thermostat Fault
96: High Feedback
Setting Value
Function
96
High Feedback
97: Low Feedback
Setting Value
Function
97
Low Feedback
9E: Low PI Auxiliary Control Level
Setting Value
Function
9E
Low PI Auxiliary Control
Level
9F: High PI Auxiliary Control Level
Setting Value
Function
9F
High PI Auxiliary Control
Level
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the PI2 Control Feedback Level is more than S3-15 [PI2 Control High Feedback Lvl].
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the output current limit is limiting the drive output speed.
V/f
OLV/PM EZOLV
OLV/PM
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive is in an LOP [Loss of Prime] condition.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the terminal set for H1-xx = 88 [MFDI Function Selection = Thermostat Fault] is active.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive is in a High Feedback Condition as specified by Y1-11 [High Feedback Level] and Y1-12
[High Feedback Lvl Fault Dly Time] and when the drive detects an HFB [High Feedback Sensed] fault or an HIFB [High Feedback
Sensed] alarm.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive is in a Low Feedback Condition as specified by Y1-08 [Low Feedback Level] and Y1-09 [Low
Feedback Lvl Fault Dly Time] and when the drive detects an LFB [Low Feedback Sensed] fault or an LOFB [High Feedback
Sensed] alarm.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the PI Aux Feedback Level is less than YF-09 [PI Aux Control Low Level Detect] or if the drive detects
an LOAUX [Low PI Aux Feedback Level] fault.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the PI Aux Feedback Level is more than YF-12 [PI Aux Control High Level Detect] or if the drive
detects an HIAUX [High PI Aux Feedback Level] fault.
2.8 H: Terminal Functions
Description
Description
Description
Description
Description
Description
Description
Description
Description
2
321

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents