1.10 H: Terminal Functions
No.
Name
(Hex.)
H2-66
Term M5-M6 Secondary
Function
(1B4C)
Expert
H2-67
Terminal M5-M6 Logical
Operation
(1B4D)
Expert
H2-68
Terminal M5-M6 Delay
Time
(1B4E)
Expert
H2-xx: MFDO Setting Values
Setting Value
Function
0
During Run
1
Zero Speed
2
Speed Agree 1
3
User-Set Speed Agree 1
4
Frequency Detection 1
5
Frequency Detection 2
6
Drive Ready
7
DC Bus Undervoltage
60
V/f
OLV/PM EZOLV
OLV/PM
Sets the second function for terminal M5-M6. Outputs the logical calculation results of the
terminals assigned to functions by H2-03 [Terminal M5-M6 Function Select].
V/f
OLV/PM
OLV/PM EZOLV
Sets the logical operation for the functions set in H2-03 [Term M5-M6 Function Selection]
and H2-66 [Term M5-M6 Secondary Function].
V/f
OLV/PM EZOLV
OLV/PM
Sets the minimum on time used to output the logical calculation results from terminal M5-
M6.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when you input a Run command and when the drive is outputting voltage.
ON : Drive is running
OFF : Drive is stopping
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency < E1-09 [Minimum Output Frequency].
Note:
Parameter E1-09 is the reference in all control methods.
ON : Output frequency < E1-09.
OFF : Output frequency ≥ E1-09.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree
Detection Width].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of "frequency reference ± L4-02".
OFF : The output frequency does not align with the frequency reference although the drive is running.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02
[Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ± L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" or the range of frequency reference ± L4-02.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the output frequency > "L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree
Detection Width]". After the terminal deactivates, the terminal stays deactivated until the output frequency is at the
value of L4-01.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency < L4-01, or the output frequency ≤ "L4-01 + L4-02"
OFF : The output frequency > "L4-01 + L4-02"
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the output frequency > L4-01 [Speed Agree Detection Level]. After the terminal activates,
the terminal stays activated until the output frequency is at the value of "L4-01 - L4-02 [Speed Agree Detection
Width]".
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency > L4-01
OFF : The output frequency < "L4-01 - L4-02", or the output frequency ≤ L4-01
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive is ready and running.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the DC bus voltage or control circuit power supply is at the voltage set in L2-05
[Undervoltage Detection Lvl (Uv1)] or less. The terminal also activates when there is a fault with the DC bus voltage.
ON : The DC bus voltage ≤ L2-05
OFF : The DC bus voltage > L2-05
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
Ref.
(Range)
F
308
(0 - FF)
0
308
(0 - 8)
0.1 s
308
(0.0 - 25.0 s)
Ref.
308
308
309
309
310
310
311
311