YASKAWA HV600 Manual page 303

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Setting Value
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
*1
F
Not Used
10
Alarm
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
18
Torque Detection 2 (N.O.)
19
Torque Detection 2 (N.C.)
1A
During reverse
1B
During Baseblock (N.C.)
1C
Motor 2 Selected
1E
Executing Auto-Restart
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-Alarm (oH)
21
Safe Torque OFF
2F
Maintenance Notification
30
During Torque Limit
37
During Frequency Output
38
Drive Enabled
39
Watt Hour Pulse Output
3A
Drive Overheat Alarm
3D
During Speed Search
42
Pressure Reached
4A
During KEB Ride-Thru
4B
During Short Circuit Braking
4C
During Fast Stop
4D
oH Pre-Alarm Reduction Limit
51
Sequence Timer 1
52
Sequence Timer 2
53
Sequence Timer 3
54
Sequence Timer 4
*1
Inverse output is not available.
*2
You cannot set this parameter on models 2169 to 2273 and 4065 to 4302.
Extended MFDO1 to MFDO3 Function Selection
You can set MFDO functions to bit 0 to bit 2 [MEMOBUS MFDO1 to 3] of MEMOBUS register 15E0 (Hex.). Use
H2-40 to H2-42 [Mbus Reg 15E0h bit0 to bit2 Output Func] to select the function.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Function
Reference
312
312
312
312
312
312
312
313
313
314
314
315
315
315
316
316
316
316
316
317
317
317
317
317
318
318
318
318
318
319
319
319
319
319
319
319
320
Setting Value
Function
58
UL6 Underload Detected
60
Internal Cooling Fan Failure
61
Pole Position Detection Complete
62
Modbus Reg 1 Status Satisfied
63
Modbus Reg 2 Status Satisfied
69
External Power 24V Supply
6A
Data Logger Error
71
Low PI2 Control Feedback Level
72
High PI2 Control Feedback Level
89
Output Current Lim
90 to 92
DWEZ Digital Outputs 1 to 3
94
Loss of Prime
95
Thermostat Fault
96
High Feedback
97
Low Feedback
9E
Low PI Auxiliary Control Level
9F
High PI Auxiliary Control Level
A9
RELAY Operator Control
AA
Utility Delay
AB
Thrust Mode
AC
Setpoint Not Maintained
B2
BAS Interlock
B8
Pump Fault
B9
Transducer Loss
BA
PI Auxiliary Control Active
BB
Differential Feedback Exceeded
BC
Sleep Active
BD
Start Delay
BE
Pre-Charge
C0
HAND Mode
C1
AUTO Mode
C2
OFF Mode
C3
Main Feedback Lost
C4
Backup Feedback Lost
Inverse Outputs of 0 to C4
Sets an inverse output of the function for the MFDO.
100 to 1C4
Put a 1 at the front of the function setting to set inverse
output. For example, set 138 for inverse output of 38
[Drive Enabled].
2.8 H: Terminal Functions
Reference
320
320
320
320
320
320
320
320
321
321
321
321
321
321
321
321
321
322
322
322
322
322
322
322
322
322
323
323
323
323
323
323
323
323
324
303
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents