Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-09 = 2] or 0 mA [H3-09 =
3] is input.
H3-40: Mbus Reg 15C1h Input Function
No.
Name
(Hex.)
H3-40
Mbus Reg 15C1h Input
Function
(0B5C)
Uses the MFAI function from MEMOBUS/Modbus communications to set the input for the function in MEMOBUS/
Modbus register 15C1.
Refer to H3-xx "MFAI Setting Values" for the setting values.
H3-41: Mbus Reg 15C2h Input Function
No.
Name
(Hex.)
H3-41
Mbus Reg 15C2h Input
Function
(0B5F)
Uses the MFAI function from MEMOBUS/Modbus communications to set the input for the function in MEMOBUS/
Modbus register 15C2.
Refer to H3-xx "MFAI Setting Values" for the setting values.
H3-42: Mbus Reg 15C3h Input Function
No.
Name
(Hex.)
H3-42
Mbus Reg 15C3h Input
Function
(0B62)
Uses the MFAI function from MEMOBUS/Modbus communications to set the input for the function in MEMOBUS/
Modbus register 15C3.
Refer to H3-xx "MFAI Setting Values" for the setting values.
H3-43: Mbus Reg Inputs FilterTime Const
No.
Name
(Hex.)
H3-43
Mbus Reg Inputs FilterTime
Const
(117F)

MFAI Setting Value

This section gives information about the functions set with H3-02 and H3-10.
0: Frequency Reference
Setting Value
Function
0
Frequency Reference
• You can copy the configuration to more than one of the analog input terminals A1 and A2. When you set more than
one analog input terminal with the master frequency reference, the sum value becomes the frequency bias.
• If you use this function to set the analog input value as the master frequency reference, set b1-01 = 1 [Frequency
Reference Selection 1 = Analog Input]. This setting value is the default value for terminals A1 and A2.
• The frequency reference is the sum of the input values for terminals A1 and A2 when you use them at the same
time. For example, when you input a 20% bias to terminal A2 and input a frequency reference of 50% from
terminal A1, the calculated frequency reference will be 70% of the maximum output frequency.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the MEMOBUS AI1 function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the MEMOBUS AI2 function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the MEMOBUS AI3 function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the time constant to apply a primary delay filter to the MEMOBUS analog input register values.
V/f
OLV/PM EZOLV
OLV/PM
The input value from the MFAI terminal set with this function becomes the master frequency reference.
Description
Description
Description
Description
Description
2.8 H: Terminal Functions
Default
(Range)
F
(4 - 2E)
Default
(Range)
F
(4 - 2E)
Default
(Range)
F
(4 - 2E)
Default
(Range)
0.00 s
(0.00 - 2.00 s)
329