10.11 L: Protection Functions
No.
Name
(Hex.)
L6-04
Torque Detection
Selection 2
(04A4)
L6-05
Torque Detection
Level 2
(04A5)
L6-06
Torque Detection
Time 2
(04A6)
L6-07
Torque Detection
Filter Time
(04E5)
L6-08
Mechanical
Fatigue Detect
(0468)
Select
L6-09
Mech Fatigue
Detect Speed Level Sets the speed level as a percentage where the drive will operate the
(0469)
L6-10
Mech Fatigue
Detect Delay Time Sets the time for mechanical deterioration detection.
(046A)
L6-11
Mech Fatigue Hold
Off Time
(046B)

L7: Torque Limit

No.
Name
(Hex.)
L7-01
Forward Torque
Limit
(04A7)
RUN
L7-02
Reverse Torque
Limit
(04A8)
RUN
L7-03
Forward
Regenerative Trq
(04A9)
Limit
RUN
574
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed range that detects overtorque and undertorque and the
operation of drives (operation status) after detection.
0 : Disabled
1 : oL @ Speed Agree - Alarm only
2 : oL @ RUN - Alarm only
3 : oL @ Speed Agree - Fault
4 : oL @ RUN - Fault
5 : UL @ Speed Agree - Alarm only
6 : UL @ RUN - Alarm only
7 : UL @ Speed Agree - Fault
8 : UL @ RUN - Fault
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for Overtorque/Undertorque Detection 2. In
V/f control, drive rated output current = 100% value. In vector
control, motor rated torque = 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for Overtorque/Undertorque Detection 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant for a primary filter to the torque reference or
to the output current used to detect overtorque/undertorque.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed where the drive detects mechanical deterioration and
how the drive operates (operation status) after detection.
0 : Disabled
1 : oL5 @ Speed > L6-09 - Alarm
2 : oL5 @ lSpeedl > L6-09 - Alarm
3 : oL5 @ Speed > L6-09 - Fault
4 : oL5 @ lSpeedl > L6-09 - Fault
5 : UL5 @ Speed < L6-09 - Alarm
6 : UL5 @ lSpeedl < L6-09 - Alarm
7 : UL5 @ Speed < L6-09 - Fault
8 : UL5 @ lSpeedl < L6-09 - Fault
V/f
CL-V/f
OLV
CLV
AOLV
mechanical deterioration detection function, with E1-04 [Maximum
Output Frequency] is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time that the drive will start mechanical deterioration
detection triggered by the cumulative operation time of the drive.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for forward motoring as a percentage,
where motor rated torque is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for reversed motoring as a percentage,
where motor rated torque is the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the torque limit value for forward regenerative conditions as a
percentage of the motor rated torque.
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
Ref.
(Range)
0
972
(0 - 8)
150%
973
(0 - 300%)
0.1 s
973
(0.0 - 10.0 s)
0 ms
973
(0 - 1000 ms)
0
973
(0 - 8)
110.0%
974
(-110.0 - +110.0%)
0.1 s
974
(0.0 - 10.0 s)
0 h
974
(0 - 65535 h)
Default
Ref.
(Range)
200%
975
(0 - 300%)
200%
975
(0 - 300%)
200%
976
(0 - 300%)