1.10 H: Terminal Functions
Setting Value
Function
9F
DWEZ Disable
A8
PI2 Control Disable
AA
PI2 Control Inverse
Operation
AB
PI2 Control Integral Reset
AC
PI2 Control Integral Hold
AD
Select PI2 Control PI
Parameters
AF
Emergency Override
FWD
B0
Emergency Override
REV
B1
Customer Safeties
B2
BAS Interlock
B8
Low City Pressure
B9
Disable Pre-charge
188
!Thermostat Fault
1A8
!PI2 Control Disable
1B8
!Low City Pressure
58
V/f
OLV/PM
OLV/PM EZOLV
Sets operation of the DriveWorksEZ program saved in the drive.
ON : Disable
OFF : Enabled
Note:
Set A1-07 = 2 [DriveWorksEZ Function Selection = Digital input] to use this function.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to disable the PI2 Control function. Parameter S3-12 [PI2 Control Disable Mode Sel] sets the
output performance.
ON : Enabled
OFF : Disabled
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to change the sign of the PI2 Control input.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to reset the PI2 Control integral value.
Note:
This input has priority over H1-xx = AC [MFDI Function Selection = PI2 Control Integral Hold].
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to lock the PI2 Control integral value.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to use the S3-06 [PI2 Control Proportional Gain] and S3-07 [PI2 Control Integral Time] values
instead of the b5-02 [Proportional Gain (P)] and b5-03 [Integral Time (I)] values. Set S3-01 = 0 [PI2 Control Enable
Selection = Disabled] to enable this function.
Note:
This multi-function input does not have an effect on PI2 Control. Use this input for the primary PI controller (b5-
xx).
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to use the speed set in S6-02 [Emergency Override Ref Selection] to run the drive in the forward
direction.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to use the speed set in S6-02 [Emergency Override Ref Selection] to run the drive in the reverse
direction.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to show that customer safeties are in place.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to show that the dampers are open.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to show that there is not sufficient pressure at the inlet to the pump.
OFF : Insufficient pressure is present on the inlet to the pump
Note:
When Y1-01 = 3 [Multiplex Mode = Memobus Network], this function will activate on any drive in the network.
An alarm condition will cause other drives in the network to stop the operation and show a "Network Drive Error"
"Check Faulted Drive" message.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to disable the Pre-charge function.
ON : Pre-charge function is disabled
V/f
OLV/PM
OLV/PM EZOLV
Sets the drive to show the VLTS [Thermostat Fault] when the input terminal is OFF.
Note:
This function is active when the drive is running.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to disable the PI2 Control function. Parameter S3-12 [PI2 Control Disable Mode Sel] sets the
output performance.
ON : Disabled
OFF : Enabled
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to show that there is not sufficient pressure at the inlet to the pump.
ON : Insufficient pressure is present on the inlet to the pump
Note:
When Y1-01 = 3 [Multiplex Mode = Memobus Network], this function will activate on any drive in the network.
An alarm condition will cause other drives in the network to stop the operation and show a "Network Drive Error"
"Check Faulted Drive" message.
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Ref.
300
301
301
301
301
301
301
301
301
302
302
302
302
302
302