E9: Motor Setting - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Note:
When you set this parameter, also set E5-24 = 0.0. The drive will detect oPE08 [Parameter Selection Error] in these conditions:
• E5-09 = 0.0 and E5-24 = 0.0
• E5-09 ≠ 0.0 and E5-24 ≠ 0.0
E5-24: PM Back-EMF L-L Vrms (mV/rpm)
No.
Name
(Hex.)
E5-24
PM Back-EMF L-L Vrms
(mV/rpm)
(0353)
Set this parameter when you use an SPM motor.
PM motor Auto-Tuning automatically sets this parameter to the value of [Back-EMF Voltage Constant (Ke)].
When E5-01 = FFFF, only set E5-09 [PM Back-EMF Vpeak (mV/(rad/s))] or E5-24 as the induced voltage constant.
Note:
When you set this parameter, also set E5-09 = 0.0. The drive will detect oPE08 [Parameter Selection Error] in these conditions:
• E5-09 = 0.0 and E5-24 = 0.0
• E5-09 ≠ 0.0 and E5-24 ≠ 0.0

E9: Motor Setting

E9 parameters set SynRM motors. Set these parameters to derate torque applications when a high level of
responsiveness and accurate speed control are not necessary. Auto-Tuning the drive will automatically set the E9
parameters.
If you cannot do EZ Tuning, you can also manually set the E9 parameters.
E9-01: Motor Type Selection
No.
Name
(Hex.)
E9-01
Motor Type Selection
(11E4)
EZ Tuning automatically sets this parameter to the value of [Motor Type Selection].
0 : Induction (IM)
1 : Permanent Magnet (PM)
2 : Synchronous Reluctance (SynRM)
E9-02: Maximum Speed
No.
Name
(Hex.)
E9-02
Maximum Speed
(11E5)
EZ Tuning automatically sets this parameter to the value of [Motor Max Revolutions].
E9-03: Rated Speed
No.
Name
(Hex.)
E9-03
Rated Speed
(11E6)
EZ Tuning automatically sets this parameter to the value of [Rated Speed].
Note:
Set E9-01 = 0 [Motor Type Selection = Induction (IM)] before you set this parameter.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the RMS value for PM motor line voltage.
V/f
OLV/PM EZOLV
OLV/PM
Sets the type of motor.
V/f
OLV/PM EZOLV
OLV/PM
Sets the maximum speed of the motor.
V/f
OLV/PM EZOLV
OLV/PM
Sets the rated rotation speed of the motor.
Description
Description
Description
Description
2.6 E: Motor Parameters
Default
(Range)
-1
0.1 mV/min
(0.0 - 6500.0 mV/min
-1
)
Default
(Range)
0
(0 to 2)
Default
(Range)
Determined by E9-01
(40.0 - 120.0 Hz)
Default
(Range)
Determined by E9-01
(100 - 7200 min
-1
)