YASKAWA HV600 Manual page 594

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

4.5 Control Circuit Wiring
Figure 4.24 Tightening Torque Display Location (Reverse Side of Front Cover)
Figure 4.25 Tightening Torque Display Location (Lower Front Side of Front Cover)
Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control circuit terminal block.
Use crimp ferrules on the wire ends to make the wiring procedure easier and more reliable.
Terminal
Terminal
Block
TB1
+V, AC, A1, A2, FM
TB3
AM, AC, S1 - S7
TB4
SN, SC, SP, +P
TB5
SN, HC, H1, H2
TB6
AC, D+, D-, PS
TB7
MA, MB, MC, M1 - M6
TB2
FE
594
Table 4.9 Control Circuit Wire Gauges and Tightening Torques
Tightening Torque
Screw Size
N∙m (in∙lb)
0.5 - 0.6
(4.4 - 5.3)
M3
1.0 - 1.2
(8.85 - 10.62)
Bare Wire
Recommended
Applicable Gauge
Gauge
mm
2
(AWG)
2
mm
(AWG)
Stranded wire:
0.25 - 1.5
0.75
(24 - 16)
(18)
Solid wire:
0.25 - 1.5
(24 - 16)
Stranded wire:
0.12 - 0.75
0.75
(26 - 18)
(18)
Solid wire:
0.2 - 1.5
(26 - 16)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Crimp Ferrule
Recommended
Applicable Gauge
Gauge
mm
2
(AWG)
2
mm
(AWG)
0.75
0.25 - 1.5
(18)
(24 - 16)
0.75
0.25 - 1.5
(18)
(24 - 16)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents