13: Speed Agree 2
Setting Value
Function
13
Speed Agree 2
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of "frequency reference ± L4-04".
OFF : The output frequency is not in the range of "frequency reference ± L4-04".
L4-04:
14: User-Set Speed Agree 2
Setting Value
Function
14
User-Set Speed Agree 2
Note:
The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is in the range of "L4-03 ± L4-04" and the range of frequency reference ±
L4-04.
OFF : The output frequency is not in the range of "L4-03 ± L4-04" or the range of frequency
reference ± L4-04.
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection Width
(+/-)].
Figure 2.65 Speed Agree 2 Time Chart
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level (+/-)] ± L4-04 [Speed
Agree Detection Width (+/-)] and in the range of the frequency reference ± L4-04.