L3: Stall Prevention

No.
Name
(Hex.)
L3-01
Stall Prevention during
Accel
(048F)
L3-02
Stall Prevent Level during
Accel
(0490)
L3-03
Stall Prevent Limit during
Accel
(0491)
L3-04
Stall Prevention during
Decel
(0492)
L3-05
Stall Prevention during
RUN
(0493)
L3-06
Stall Prevent Level during
Run
(0494)
L3-11
Overvoltage Suppression
Select
(04C7)
L3-17
DC Bus Regulation Level
(0462)
L3-20
DC Bus Voltage
Adjustment Gain
(0465)
Expert
L3-21
OVSuppression Accel/
Decel P Gain
(0466)
Expert
L3-22
PM Stall Prevention
Decel Time
(04F9)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the method of Stall Prevention During Acceleration.
0 : Disabled
1 : Enabled
2 : Intelligent (Ignore Decel Ramp)
V/f
OLV/PM EZOLV
OLV/PM
Sets the output current level to activate the Stall Prevention function during acceleration as
a percentage of the drive rated output current.
V/f
OLV/PM
OLV/PM EZOLV
Sets the lower limit for the stall prevention level used in the constant output range as a
percentage of the drive rated output current.
V/f
OLV/PM EZOLV
OLV/PM
Sets the method that the drive will use to prevent overvoltage faults when decelerating.
Note:
The setting range changes when the A1-02 [Control Method Selection] value changes:
• When A1-02 = 5 [OLV/PM], the setting range is 0 to 2.
• When A1-02 = 8 [EZOLV], the setting range is 0, 1.
0 : Disabled
1 : General Purpose
2 : Intelligent (Ignore Decel Ramp)
4 : Overexcitation/High Flux
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to enable and disable Stall Prevention During Run.
Note:
• An output frequency lower than 6 Hz will disable Stall Prevention during Run. The
L3-05 and L3-06 [Stall Prevent Level during Run] settings do not have an effect.
• The default setting changes when the A1-02 [Control Method] value changes:
–A1-02 = 0, 5 [V/f, OLV/PM]: 2
–A1-02 = 8 [EZOLV]: 3
0 : Disabled
1 : Deceleration Time 1 (C1-02)
2 : Deceleration Time 2 (C1-04)
3 : Intelligent (Ignore Decel Ramp)
V/f
OLV/PM
OLV/PM EZOLV
Sets the output current level to enable the Stall Prevention function during operation as a
percentage of the drive rated output current.
Note:
This parameter is applicable when L3-05 = 1, 2 [Stall Prevention during RUN =
Deceleration Time 1 (C1-02), Deceleration Time 2 (C1-04)].
V/f
OLV/PM EZOLV
OLV/PM
Sets the overvoltage suppression function.
0 : Disabled
1 : Enabled
V/f
OLV/PM EZOLV
OLV/PM
Sets the target value for the DC bus voltage when the overvoltage suppression function and
the Decel Stall Prevention function (Intelligent Stall Prevention) are active.
V/f
OLV/PM EZOLV
OLV/PM
Sets the proportional gain used to control the DC bus voltage.
V/f
OLV/PM EZOLV
OLV/PM
Sets the proportional gain to calculate acceleration and deceleration rates.
V/f
OLV/PM EZOLV
OLV/PM
Sets the momentary deceleration time that the drive will use when it tries to accelerate a
PM motor and detected motor stalls. This function is applicable when L3-01 = 1 [Stall
Prevent Select duringAccel = General Purpose].
1.11 L: Protection Functions
Default
Ref.
(Range)
1
361
(0 - 2)
Determined by L8-38
362
(0 - 120%)
50%
362
(0 - 100%)
1
363
(Determined by A1-02)
Determined by A1-02
364
(0 - 3)
Determined by L8-38
364
(5 - 120%)
0
365
(0, 1)
208 V Class: 375 V,
365
480 V Class: 750 V
(208 V Class: 150 - 400
V,
480 V Class: 300 - 800
V)
Determined by A1-02
365
(0.00 - 5.00)
1.00
366
(0.10 - 10.00)
0.0 s
366
(0.0 - 6000.0 s)
1
79