2.7 F: Options
Register
No. (Hex.)
Drive Status (Drive 1)
bit 0
During Run
bit 1
During Reverse Run
bit 2
Drive ready
bit 3
Fault
bit 4
Frequency Reference Setting Fault
bit 5
No response from slave
bit 6
Communication Error
15E7
bit 7
No response from slave 10 consecutive attempts.
bit 8
Communication fault occurred 10 consecutive times.
bit 9
Receive broadcast command while drive is running
bit A
Communication error with master drive
bit B -
Reserved
D
bit E
ComRef status
bit F
ComCtrl status
Output frequency or frequency reference (Drive Status Bit 1: ON) (Drive
1)
15E8
Drive Status Bit 4 = 0 [Output Frequency]
Drive Status Bit 4 = 1 [Frequency Reference]
15E9
Drive Status (Drive 2)
Output frequency or frequency reference (Drive Status Bit 4: ON) (Drive
15EA
2)
15EB
Drive Status (Drive 3)
Output frequency or frequency reference (Drive Status Bit 4: ON) (Drive
15EC
3)
15ED
Drive Status (Drive 4)
Output frequency or frequency reference (Drive Status Bit 4: ON) (Drive
15EE
4)
268
Table 2.45 Monitor Data
Description
1: Upper/Lower Limit Fault
1: Response has timed out.
1: The drive detected a fault from a slave.
1: Timeout occurred 10 consecutive times.
1: Fault has occurred from a slave 10 consecutive times.
1: Drive operates as specified by the broadcast message command.
1: The slave cannot communicate with the master because of a communication error.
The unit of measure changes when o1-03 changes.
Outputs when:
• Normal operation: Output frequency
• Drive detects Frequency Reference Setting Fault: Frequency reference when the error
occurs
Clears the value when the drive detects a communication error or communication stops.
Refer to "15E7: Drive Status (Drive 1)" for more information.
The unit of measure changes when o1-03 changes.
Outputs when:
• Normal operation: Output frequency
• Drive detects Frequency Reference Setting Fault: Frequency reference when the error
occurs
Clears the value when the drive detects a communication error or communication stops.
Refer to "15E7: Drive Status (Drive 1)" for more information.
The unit of measure changes when o1-03 changes.
Outputs when:
• Normal operation: Output frequency
• Drive detects Frequency Reference Setting Fault: Frequency reference when the error
occurs
Clears the value when the drive detects a communication error or communication stops.
Refer to "15E7: Drive Status (Drive 1)" for more information.
The unit of measure changes when o1-03 changes.
Outputs when:
• Normal operation: Output frequency
• Drive detects Frequency Reference Setting Fault: Frequency reference when the error
occurs
Clears the value when the drive detects a communication error or communication stops.