1.18 U: Monitors
No.
Name
(Hex.)
U1-11
Output Terminal Status
(004A)
U1-12
Drive Status
(004B)
U1-13
Terminal A1 Level
(004E)
U1-14
Terminal A2 Level
(004F)
U1-16
SFS Output Frequency
(0053)
U1-18
oPE Fault Parameter
(0061)
U1-19
MEMOBUS/Modbus Error
Code
(0066)
U1-25
SoftwareNumber Flash
(004D)
U1-26
SoftwareNumber ROM
(005B)
U1-50
Virtual Analog Input
(1199)
Expert
U1-60
System Setpoint
(1089)
114
V/f
OLV/PM EZOLV
OLV/PM
Shows the status of the MFDO terminal where 1 = (ON) and 0 = (OFF).
For example, U1-11 shows "00000011" when terminals M1 and M3 are ON.
Note:
When H2-xx = 100 to 1C4 [Inverse Output of Function], the monitor will show the value before
inversion.
bit 0 : Terminals M1-M2
bit 1 : Terminals M3-M4
bit 2 : Terminals M5-M6
bit 3 : Not used (normal value of 0).
bit 4 : Not used (normal value of 0).
bit 5 : Not used (normal value of 0).
bit 6 : Not used (normal value of 0).
bit 7 : Fault relay MA/MB-MC
V/f
OLV/PM
OLV/PM EZOLV
Shows drive status where 1 = ON and 0 = OFF.
For example, U1-12 shows "00000101" during run with the Reverse Run command.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive ready
bit6 : During minor fault detection
bit7 : During fault detection
V/f
OLV/PM EZOLV
OLV/PM
Shows the signal level of terminal A1.
Unit: 0.1%
V/f
OLV/PM
OLV/PM EZOLV
Shows the signal level of terminal A2.
Unit: 0.1%
V/f
OLV/PM
OLV/PM EZOLV
Shows the output frequency after soft start. Shows the frequency with acceleration and deceleration
times and S-curves. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.
Unit: 0.01 Hz
V/f
OLV/PM EZOLV
OLV/PM
Shows the parameter number that caused the oPE02 [Parameter Range Setting Error] or oPE08
[Parameter Selection Error].
V/f
OLV/PM EZOLV
OLV/PM
Shows the contents of the MEMOBUS/Modbus communication error where 1 = "error" and 0 = "no
error".
For example, U1-19 shows "00000001" when there is a CRC error.
bit0 : CRC Error
bit1 : Data Length Error
bit2 : Not used (normal value of 0).
bit3 : Parity Error
bit4 : Overrun Error
bit5 : Framing Error
bit6 : Timed Out
bit7 : Not used (normal value of 0).
V/f
OLV/PM EZOLV
OLV/PM
Shows the FLASH ID.
V/f
OLV/PM EZOLV
OLV/PM
Shows the ROM ID.
V/f
OLV/PM
OLV/PM EZOLV
Shows the virtual analog input value.
V/f
OLV/PM EZOLV
OLV/PM
Shows the PID Setpoint.
Unit: 0.01%
Note:
Parameters b5-46 [PID Unit Display Selection], b5-38 [PID User Unit Display Scaling], and b5-
39 [PID User Unit Display Digits] set the unit, range, and resolution.
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
MFAO Signal Level
No signal output available
No signal output available
10 V = 100% (0 V to +10 V)
10 V = 100% (0 V to +10 V)
10 V = Maximum frequency
(0 V to +10 V)
No signal output available
No signal output available
No signal output available
No signal output available
Determined by H7-40
No signal output available

Hide quick links: