YASKAWA HV600 Manual page 178

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.3 b: Application
Figure 2.1 Example of Setting the Frequency Reference with a Voltage Signal to Terminal A1
Note:
You can also use this diagram to wire terminal A2.
• Current Input
Refer to
Table 2.21
to use a current signal input to one of the MFAI terminals.
Terminal
Signal Level
A1
4 - 20 mA
0 - 20 mA
A2
4 - 20 mA
0 - 20 mA
Figure 2.2 Example of Setting the Frequency Reference with a Current Signal to Terminal A2
Note:
You can also use this diagram to wire terminal A1.
Changing between Master and Auxiliary Frequency References
Use the multi-step speed reference function to change the frequency reference input between terminals A1 and A2.
2 : Serial Communications
The drive uses serial communications to enter the frequency reference.
3 : Option PCB
The drive uses a communications option card or input option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If b1-01 = 3, but you did not connect a communications option card, oPE05 [Run Cmd/Freq Ref Source Sel Err] will flash on the keypad.
178
Table 2.21 Frequency Reference Current Input
Parameter Settings
Signal Level
Function Selection
Selection
H3-01 = 2
H3-02 = 0
[Frequency Reference]
H3-01 = 3
H3-09 = 2
H3-10 = 0
[Frequency Reference]
H3-09 = 3
Gain
Bias
H3-03
H3-04
H3-11
H3-12
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Note
Set Jumper Switch S1 to "I" for
current input.
Set Jumper Switch S1 to "I" for
current input.