YASKAWA HV600 Manual page 410

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.11 o: Keypad-Related Settings
To display a maximum output frequency of 100.00, set parameters to these values:
• o1-10 = 10000
• o1-11 = 2 [User Units Decimal Position = 2 Dec (XXX.XX)]
Note:
Set o1-03 = 3 [Frequency Display Unit Selection = User Units (o1-10 & o1-11)] before you set o1-10 and o1-11.
o1-11: User Units Decimal Position
No.
Name
(Hex.)
o1-11
User Units Decimal Position
(0521)
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
Note:
Set o1-03 = 3 [Frequency Display Unit Selection = User Units (o1-10 & o1-11)] before you set o1-10 [User Units Maximum Value] and o1-
11.
o1-13: Freq. Reference Custom Unit 1
No.
Name
(Hex.)
o1-13
Freq. Reference Custom
Unit 1
(3105)
Refer to
Custom Units on page 207
o1-14: Freq. Reference Custom Unit 2
No.
Name
(Hex.)
o1-14
Freq. Reference Custom
Unit 2
(3106)
Refer to
Custom Units on page 207
o1-15: Freq. Reference Custom Unit 3
No.
Name
(Hex.)
o1-15
Freq. Reference Custom
Unit 3
(3107)
Refer to
Custom Units on page 207
o1-17: F3 Key Function Selection
No.
Name
(Hex.)
o1-17
F3 Key Function Selection
(3109)
0 : Standard (based on screen)
F3 key function changes when the screen shown on the keypad changes.
1 : MONITOR (shortcut)
410
V/f
OLV/PM EZOLV
OLV/PM
Sets the number of decimal places for frequency reference and monitor values.
V/f
OLV/PM
OLV/PM EZOLV
Sets the first character of the custom unit display when o1-03 = 3 [Frequency Display Unit Selection
= User Units] and o1-09 = 49 [Freq. Reference Display Units = Custom (o1-13~15)].
for more information about available selections.
V/f
OLV/PM EZOLV
OLV/PM
Sets the second character of the custom unit display when o1-03 = 3 [Frequency Display Unit
Selection = User Units] and o1-09 = 49 [Freq. Reference Display Units = Custom (o1-13~15)].
for more information about available selections.
V/f
OLV/PM EZOLV
OLV/PM
Sets the third character of the custom unit display when o1-03 = 3 [Frequency Display Unit Selection
= User Units] and o1-09 = 49 [Freq. Reference Display Units = Custom (o1-13~15)].
for more information about available selections.
V/f
OLV/PM EZOLV
OLV/PM
Sets the action when you push the F3 key and the LCD display text above the F3 key.
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
Determined by o1-03
(0 - 3)
Default
(Range)
41
(20 - 7A)
Default
(Range)
41
(20 - 7A)
Default
(Range)
41
(20 - 7A)
Default
(Range)
0
(0 - 4)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents