A8: PI2 Control Disable
Setting Value
Function
A8
PI2 Control Disable
ON : Enabled
OFF : Disabled
AA: PI2 Control Inverse Operation
Setting Value
Function
AA
PI2 Control Inverse
Operation
AB: PI2 Control Integral Reset
Setting Value
Function
AB
PI2 Control Integral Reset
AC: PI2 Control Integral Hold
Setting Value
Function
AC
PI2 Control Integral Hold
AD: Select PI2 Control PI Parameters
Setting Value
Function
AD
Select PI2 Control PI
Parameters
AF: Emergency Override FWD
Setting Value
Function
AF
Emergency Override FWD
B0: Emergency Override REV
Setting Value
Function
B0
Emergency Override REV
B1: Customer Safeties
Setting Value
Function
B1
Customer Safeties
This function is the same as H1-xx = 70 [MFDI Function Selection = Drive Enable 2], with these differences:
• When you deactivate the input, the stopping method is Coast to Stop.
• If you deactivate the input when there is a Run command, the drive will show a SAFE [Customer Safeties] alarm.
The drive will not show dnE [Drive Disabled].
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to disable the PI2 Control function. Parameter S3-12 [PI2 Control Disable Mode Sel] sets the output
performance.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to change the sign of the PI2 Control input.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to reset the PI2 Control integral value.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to lock the PI2 Control integral value.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to use the S3-06 [PI2 Control Proportional Gain] and S3-07 [PI2 Control Integral Time] values instead of the
b5-02 [Proportional Gain (P)] and b5-03 [Integral Time (I)] values. Set S3-01 = 0 [PI2 Control Enable Selection = Disabled] to
enable this function.
V/f
OLV/PM
OLV/PM EZOLV
Sets the command to use the speed set in S6-02 [Emergency Override Ref Selection] to run the drive in the forward direction.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to use the speed set in S6-02 [Emergency Override Ref Selection] to run the drive in the reverse direction.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to show that customer safeties are in place.
2.8 H: Terminal Functions
Description
Description
Description
Description
Description
Description
Description
Description
2