B: Application; B1: Operation Mode Selection - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.3

b: Application

b parameters set these functions:
• Frequency reference source/Run command source
• Stopping method settings
• DC Injection Braking
• Speed Search
• Timer Function
• PID control
• Energy Savings Control

b1: Operation Mode Selection

b1 parameters set the operation mode for the drive.
b1-01: Frequency Reference Selection 1
No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
Note:
• Push
on the keypad to set the input mode to HAND and enter the frequency reference from the keypad.
• When the drive receives a Run command when the frequency reference is 0 Hz or less than the E1-09 [Minimum Output Frequency] value,
on the keypad will flash. Examine the setting for the frequency reference input and enter a value ≥ E1-09.
0 : Keypad
The drive uses the keypad to enter the frequency reference and also switches the PID setpoint to YA-01 [Setpoint 1].
Use
and
on the keypad to change the frequency reference.
1 : Analog Input
The drive uses MFAI terminals A1 and A2 to input an analog frequency reference with a voltage or current input
signal.
• Voltage Input
Refer to
Table 2.20
to use a voltage signal input to one of the MFAI terminals.
Terminal Signal
Terminal
Level
A1
0 - 10 V
A2
0 - 10 V
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the input method for the frequency reference.
Table 2.20 Frequency Reference Voltage Input
Parameter Settings
Signal Level
Function Selection
Selection
H3-01 = 0
H3-02 = 0
[Frequency Reference]
H3-09 = 0
H3-10 = 0
[Frequency Reference]
Description
Gain
Bias
H3-03
H3-04
H3-11
H3-12

2.3 b: Application

Default
(Range)
1
(0 - 3)
Note
Set Jumper Switch S1 to "V" for
voltage input.
Set Jumper Switch S1 to "V" for
voltage input.
2
177

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents