YASKAWA HV600 Manual page 293

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

3E: PID Setpoint Selection 1
Setting Value
Function
3E
PID Setpoint Selection 1
Note:
If you use this function and one of H1-xx = 83 to 85 [Dedicated Multi-Setpoint YA-02 to YA-04] at the same time, the drive will detect an
oPE03 [Multi-Function Input Setting Err].
ON : YA-02 or YA-04 is PID setpoint.
OFF : The frequency reference, YA-01 [Setpoint 1], or YA-03 [Setpoint 3] is PID setpoint.
3F: PID Setpoint Selection 2
Setting Value
Function
3F
PID Setpoint Selection 2
Note:
If you use this function and one of H1-xx = 83 to 85 [Dedicated Multi-Setpoint YA-02 to YA-04] at the same time, the drive will detect an
oPE03 [Multi-Function Input Setting Err].
ON : YA-03 or YA-04 is PID setpoint.
OFF : The frequency reference, YA-01 [Setpoint 1], or YA-02 [Setpoint 2] is PID setpoint.
40: Forward RUN (2-Wire)
Setting Value
Function
40
Forward RUN (2-Wire)
ON : Forward Run
OFF : Run Stop
Note:
• Turning ON the Forward Run command terminal and the Reverse Run command terminal will cause alarm EF [FWD/REV Run Command
Input Error] and the motor will ramp to stop.
• Initialize the drive with a 2-wire sequence to set the Forward Run command to terminal S1.
• This function will not operate at the same time as H1-xx = 42, 43 [Run Command/FWD/REV Command (2-Wire Seq 2)].
41: Reverse RUN (2-Wire)
Setting Value
Function
41
Reverse RUN (2-Wire)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to switch the PID setpoint to YA-02 [Setpoint 2] or YA-04 [Setpoint 4]. Set this function and H1-xx = 3F [PID
Setpoint Selection 2] at the same time.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to switch the PID setpoint to YA-03 [Setpoint 3] or YA-04 [Setpoint 4]. Set this function and H1-xx = 3E [PID
Setpoint Selection 1] at the same time.
V/f
OLV/PM EZOLV
OLV/PM
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 41 [Reverse Run Command (2-Wire Seq)]
together.
Figure 2.54 2-Wire Sequence Wiring Example
V/f
OLV/PM EZOLV
OLV/PM
Sets the Forward Run command for 2-wire sequence 1. Set this function and H1-xx = 40 [Forward Run Command (2-Wire Seq)]
together.
2.8 H: Terminal Functions