YASKAWA HV600 Manual page 61

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Setting Value
Function
8
During Baseblock (N.O.)
9
Frequency Reference
from Keypad
B
Torque Detection 1 (N.
O.)
C
Frequency Reference
Loss
E
Fault
F
Not Used
10
Alarm
11
Fault Reset Command
Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : During baseblock
OFF : The drive is not in baseblock.
V/f
OLV/PM EZOLV
OLV/PM
Shows the selected frequency reference source.
ON : The keypad is the frequency reference source.
OFF : Parameter b1-01 [Frequency Reference Selection 1] is the frequency reference source.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive detects overtorque or undertorque.
ON : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque < L6-02 for longer
than the time set in L6-03 [Torque Detection Time 1].
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive detects a loss of frequency reference.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects a fault.
Note:
The terminal will not activate for CPF00 and CPF01 [Control Circuit Error] faults.
V/f
OLV/PM
OLV/PM EZOLV
Use this setting for unused terminals or to use terminals in through mode. Also use this setting as the PLC contact
output via MEMOBUS/Modbus or the communication option. This signal does not function if you do not configure
signals from the PLC.
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the drive detects a minor fault.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial
communications, or the communication option.
V/f
OLV/PM
OLV/PM EZOLV
Use this setting when the drive uses the timer function as an output terminal.
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree
Detection Width (+/-)].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency is in the range of "frequency reference ± L4-04".
OFF : The output frequency is not in the range of "frequency reference ± L4-04".
V/f
OLV/PM EZOLV
OLV/PM
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level (+/-)] ± L4-04
[Speed Agree Detection Width (+/-)] and in the range of the frequency reference ± L4-04.
Note:
The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency is in the range of "L4-03 ± L4-04" and the range of frequency reference ± L4-04.
OFF : The output frequency is not in the range of "L4-03 ± L4-04" or the range of frequency reference ± L4-04.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the output frequency > "L4-03 [Speed Agree Detection Level (+/-)] + L4-04 [Speed
Agree Detection Width (+/-)]". After the terminal deactivates, the terminal stays deactivated until the output frequency
is at the value of L4-03.
Note:
The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency < L4-03, or the output frequency ≤ L4-03 + L4-04.
OFF : The output frequency > "L4-03 + L4-04".
V/f
OLV/PM
OLV/PM EZOLV
The terminal activates when the output frequency > L4-03 [Speed Agree Detection Level (+/-)]. After the terminal
activates, the terminal stays activated until the output frequency is at the value of "L4-03 - L4-04".
Note:
The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
ON : The output frequency > L4-03.
OFF : The output frequency < "L4-03 - L4-04", or the output frequency ≤ L4-03.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque > L6-02 [Torque Detection Level 1], or the output current/torque < L6-02 for longer
than the time set in L6-03 [Torque Detection Time 1].
1.10 H: Terminal Functions
Description
Ref.
311
311
312
312
312
312
312
312
312
313
313
314
314
1
315
61