2011, 2017, 4005, 4008
E : Const Trq, 60 Hz base, 180 Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 208 V class drives. Multiply the values by 2 for 480 V class drives.
2011, 2017, 4005, 4008
F : Custom
Set E1-04 to E1-13 [V/f Pattern for Motor 1] to set the values for this custom pattern.
The default settings are the same as setting value 1 [Const Trq, 60Hz base, 60Hz max].
E1-04: Maximum Output Frequency
No.
Name
(Hex.)
E1-04
Maximum Output Frequency
(0303)
E1-05: Maximum Output Voltage
No.
Name
(Hex.)
E1-05
Maximum Output Voltage
(0304)
E1-06: Base Frequency
No.
Name
(Hex.)
E1-06
Base Frequency
(0305)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
2024 - 2169, 4011 - 4077
2024 - 2169, 4011 - 4077
V/f
OLV/PM EZOLV
OLV/PM
Sets the maximum output frequency for the V/f pattern.
V/f
OLV/PM EZOLV
OLV/PM
Sets the maximum output voltage for the V/f pattern.
V/f
OLV/PM EZOLV
OLV/PM
Sets the base frequency for the V/f pattern.
Description
Description
Description
2.6 E: Motor Parameters
2211 - 2273, 4096 - 4302
2211 - 2273, 4096 - 4302
Default
(Range)
Determined by A1-02 and
E5-01
(Determined by A1-02 and
E5-01)
Default
(Range)
208 V Class: 230.0 V,
480 V Class: 460.0 V
(208 V Class: 0.0 - 255.0 V,
480 V Class: 0.0 - 510.0 V)
Default
(Range)
Determined by A1-02 and
E5-01
(0.0 - E1-04)