0 : FWD/Stop, REV/Stop
The drive uses bit 0 in command data 0001H of the MEMOBUS register in the motor forward Run command (bit 0 =
1) and the stop command (bit 0 = 0). The drive uses bit 1 in the motor reverse Run command (bit 1 = 1) and the stop
command (bit 1 = 0).
1 : Run/Stop, FWD/REV
The drive uses bit 0 in command data 0001H of the MEMOBUS register in the motor Run command (bit 0 = 1) and
the stop command (bit 0 = 0). The drive uses bit 1 in the direction of motor rotation command (Forward run (bit1 = 0)
or Reverse run (bit 1 = 1)).
H5-14: BACnet Device Obj ID LOW BITS
No.
Name
(Hex.)
H5-14
BACnet Device Obj ID
LOW BITS
(310D)
This parameter and H5-15 [BACnet Device Obj ID HIGH BITS] set the Instance Identifier of the BACnet Device
Object. The H5-14 value is the least significant word and the H5-15 value is the most significant word. Refer to these
examples to set H5-14 and H5-15 correctly:
• Example 1: Set Device Object Instance Identifier of "1234"
The number of 1234 (decimal) is equal to 4D2 (hexadecimal). Set H5-14 = 04D2 and H5-15 = 0000.
• Example 2: Set Device Object Instance Identifier of "1234567"
The number of 1234567 (decimal) is equal to 12D687 (hexadecimal). Set H5-14 = D687 and H5-15 = 0012.
H5-15: BACnet Device Obj ID HIGH BITS
No.
Name
(Hex.)
H5-15
BACnet Device Obj ID
HIGH BITS
(310E)
Parameter H5-14 [BACnet Device Obj ID LOW BITS] and this parameter set the Instance Identifier of the BACnet
Device Object. The H5-14 value is the least significant word and the H5-15 value is the most significant word. Refer
to these examples to set H5-14 and H5-15 correctly:
• Example 1: Set Device Object Instance Identifier of "1234"
The number of 1234 (decimal) is equal to 4D2 (hexadecimal). Set H5-14 = 04D2 and H5-15 = 0000.
• Example 2: Set Device Object Instance Identifier of "1234567"
The number of 1234567 (decimal) is equal to 12D687 (hexadecimal). Set H5-14 = D687 and H5-15 = 0012.
H5-18: Motor Speed Filter over Comms
No.
Name
(Hex.)
H5-18
Motor Speed Filter over
Comms
(11A2)
Sets the filter time constant when you monitor the output frequency or motor speed during MEMOBUS/Modbus
communications or use of the communication option.
These are the MEMOBUS registers:
• 003EH (Output Frequency)
• 003FH (Output Frequency)
• 0044H (U1-05: Motor Speed)
• 00ACH (U1-05: Motor Speed)
• 00ADH (U1-05: Motor Speed)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Sets the lower bits of the BACnet device object ID as a 4-digit hexadecimal number.
V/f
OLV/PM EZOLV
OLV/PM
Sets the upper bits of the BACnet device object ID as a 4-digit hexadecimal number.
V/f
OLV/PM EZOLV
OLV/PM
Sets the filter time constant used when monitoring motor speed during MEMOBUS/Modbus
communications or with a communication option.
Description
Description
Description
2.8 H: Terminal Functions
Default
(Range)
0001
(0000 - FFFF)
Default
(Range)
0000
(0000 - 003F)
Default
(Range)
0 ms
(0 - 100 ms)
343