YASKAWA HV600 Manual page 89

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
n8-49
Heavy Load Id Current
(053C)
n8-50
Medium Load Iq Level
(High)
(053D)
n8-51
Pull-in Current @
Acceleration
(053E)
n8-52
ACR P Gain
(053F)
Expert
n8-54
Voltage Error
Compensation Time
(056D)
Expert
n8-55
Motor to Load Inertia
Ratio
(056E)
n8-56
PM High Performance
Selection
(056F)
Expert
n8-62
Output Voltage Limit
Level
(057D)
Expert
n8-63
Output Voltage Limit P
Gain
(057E)
Expert
n8-64
Output Voltage Limit I
Time
(057F)
Expert
n8-65
Speed Fdbk Gain @ oV
Suppression
(065C)
Expert
n8-66
Output Voltage Limit
Filter Time
(0235)
Expert
n8-74
Light Load Iq Level
(05C3)
n8-75
Medium Load Iq Level
(low)
(05C4)
n8-76
Id Switching Filter Time
(05CD)
Expert
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the d-axis current to that the drive will supply to the motor to run it at a constant speed
with a heavy load. Considers E5-03 [PM Motor Rated Current (FLA)] to be 100%. Usually
it is not necessary to change this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the load current level to start high efficiency control as a percentage of E5-03 [PM
Motor Rated Current (FLA)]. Usually it is not necessary to change this setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the pull-in current allowed to flow during acceleration/deceleration as a percentage of
the motor rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5 [OLV/PM]: E5-03 [Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
V/f
OLV/PM EZOLV
OLV/PM
Sets the proportional gain of the current regulator. Usually it is not necessary to change this
setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the time constant that the drive uses when adjusting for voltage errors.
V/f
OLV/PM
OLV/PM EZOLV
Sets the ratio between motor inertia and machine inertia.
0 : Below 1:10
1 : Between 1:10 and 1:30
2 : Between 1:30 and 1:50
3 : Beyond 1:50
V/f
OLV/PM
OLV/PM EZOLV
Usually it is not necessary to change this setting. Sets the high efficiency control method
for IPM motor.
0 : Disabled
1 : Enabled (Vd)
2 : Enabled (Vd & Vq)
V/f
OLV/PM EZOLV
OLV/PM
Sets the output voltage limit to prevent saturation of the output voltage. Usually it is not
necessary to change this parameter.
Note:
• When A1-02 = 8 [Control Method Selection = EZOLV], this parameter is available in
Expert Mode.
• When A1-02 = 8, the default setting is:
–208 V Class: 230.0 V
–480 V Class: 460.0 V
V/f
OLV/PM
OLV/PM EZOLV
Sets the proportional gain for output voltage control. Usually it is not necessary to change
this setting.
V/f
OLV/PM
OLV/PM EZOLV
Sets the integral time for output voltage control. Usually it is not necessary to change this
setting.
V/f
OLV/PM EZOLV
OLV/PM
Sets the gain of internal speed feedback detection suppression while the overvoltage
suppression function is operating as a magnification value. Usually it is not necessary to
change this parameter.
V/f
OLV/PM
OLV/PM EZOLV
Sets the filter time constant for output voltage control. Usually it is not necessary to change
this setting.
V/f
OLV/PM
OLV/PM EZOLV
Set n8-48 [Pull-in/Light Load Id Current] to the percentage of load current (q-axis current)
that you will apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
V/f
OLV/PM EZOLV
OLV/PM
Set n8-78 [Medium Load Id Current] to the percentage of load current (q-axis current) that
you will apply, where E5-03 [Motor Rated Current (FLA)] = a setting value of 100%.
V/f
OLV/PM EZOLV
OLV/PM
Sets the filter time constant for d-axis current reference. Usually it is not necessary to
change this setting.
1.12 n: Special Adjustment
Default
Ref.
(Range)
Determined by E5-01
399
(-200.0 - +200.0%)
80%
399
(50 - 255%)
Determined by A1-02
399
(0 - 200%)
10.0
399
(-100.0 - 100.0)
1.00 s
400
(0.00 - 10.00 s)
0
400
(0 - 3)
1
401
(0 - 2)
208 V Class: 200.0 V,
401
480 V Class: 400.0 V
(208 V Class: 0.0 - 240.0
V,
480 V Class: 0.0 - 480.0
V)
1.00
401
(0.00 - 100.00)
0.040 s
401
(0.000 - 5.000)
1.50
401
(0.00 - 10.00)
0.020 s
402
(0.000 - 5.000)
30%
402
(0 - 255%)
50%
402
(0 - 255%)
200 ms
402
(0 - 5000 ms)
1
89

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents