2.3 b: Application
b1-11:
b1-14: Phase Order Selection
No.
Name
(Hex.)
b1-14
Phase Order Selection
(01C3)
Note:
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will not reset this parameter.
0 : Standard
1 : Switch Phase Order
b1-17: Run Command at Power Up
No.
Name
(Hex.)
b1-17
Run Command at Power Up
(01C6)
0 : Disregard Existing RUN Command
The drive does not start to operate the application when you apply power, even when there is an existing Run
command.
Enter the Run command again to operate the application.
Note:
When you energize the drive, if there is an existing Run command enabled from an external source,
1 : Accept Existing RUN Command
When there is an existing Run command, the drive starts to operate the application when you apply power.
WARNING! Sudden Movement Hazard. When you use a 3-Wire sequence, set A1-03 = 3330 [Initialize Parameters = 3-Wire
Initialization] and make sure that b1-17 = 0 [Run Command at Power Up = Disregard Existing RUN Command] (default). If you do
not correctly set the drive parameters for 3-Wire operation before you energize the drive, the motor can suddenly rotate when you
energize the drive.
b1-40: Deceleration Abort Time
No.
Name
(Hex.)
b1-40
Deceleration Abort Time
(3BCF)
186
Figure 2.14 Run Delay Memory Running & Stop
V/f
OLV/PM EZOLV
OLV/PM
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can align the
Forward Run command from the drive and the forward direction of the motor without changing
wiring.
V/f
OLV/PM EZOLV
OLV/PM
Sets drive response when you apply power to drive that has an external Run command. Set this
parameter in applications where energizing or de-energizing the drive enables the Run command.
V/f
OLV/PM EZOLV
OLV/PM
Sets the maximum time until the drive shuts off the output to decelerate to stop.
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
0
(0, 1)
Default
(Range)
1
(0, 1)
on the keypad will flash quickly.
Default
(Range)
0.0 s
(0.0 - 6000.0 s)