YASKAWA HV600 Manual page 503

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

0 : Disabled
1 : Enabled
YF-21: PI Aux Ctrl Level Unit Selection
No.
Name
(Hex.)
YF-21
PI Aux Ctrl Level Unit
Selection
(3F64)
0 : "WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : "Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom (YF-32~34)
50 : None
YF-22: PI Aux Level Decimal Place Pos
No.
Name
(Hex.)
YF-22
PI Aux Level Decimal Place
Pos
(3F65)
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
YF-23: PI Aux Ctrl Output Level Select
No.
Name
(Hex.)
YF-23
PI Aux Ctrl Output Level
Select
(3F66)
0 : Direct Acting
When the feedback is higher than the setpoint, the speed will be lower.
1 : Inverse Acting
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM EZOLV
OLV/PM
Set the units shown for the PI Aux Level parameters and monitors.
V/f
OLV/PM EZOLV
OLV/PM
Sets the number of decimal places for the PI Aux Level parameters and monitors.
V/f
OLV/PM EZOLV
OLV/PM
Sets the PI Auxiliary Controller to be Direct-acting or Inverse-acting.
2.14 Y: Application Features
Description
Description
Description
Default
(Range)
1
(0 - 50)
Default
(Range)
1
(0 - 3)
Default
(Range)
1
(0, 1)
2
503

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents