YASKAWA HV600 Manual page 418

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.11 o: Keypad-Related Settings
o2-09: Region Code
No.
Name
(Hex.)
o2-09
Reserved
(050D)
o2-19: Parameter Write during Uv
No.
Name
(Hex.)
o2-19
Parameter Write during Uv
(061F)
0 : Disabled
1 : Enabled
Note:
If you enable this parameter and use a 24 V Power Supply option that is earlier than revision B, the parameter changes can possibly not write
correctly and it can cause a CPF06 [EEPROM Memory Data Error] fault.
o2-23: External 24V Powerloss Detection
No.
Name
(Hex.)
o2-23
External 24V Powerloss
Detection
(11F8)
RUN
Note:
The drive will not run when it is operating from one 24-V external power supply.
0 : Disable
The drive does not detect the loss of the 24-V external power supply.
1 : Enabled
The keypad shows the L24v [Loss of External Power 24 Supply] indicator if the drive detects the loss of the 24-V
external power supply.
Note:
A minor fault signal is not output from H2-xx = 10 [MFDO Function Selection = Minor Fault].
o2-24: LED Light Function Selection
No.
Name
(Hex.)
o2-24
LED Light Function
Selection
(11FE)
Note:
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will not reset this parameter.
0 : Enable Status Ring & Keypad LED
1 : LED Status Ring Disable
2 : Keypad LED Light Disable
o2-26: Alarm display at ext. 24V power
No.
Name
(Hex.)
o2-26
Alarm display at ext. 24V
power
(1563)
418
-
V/f
OLV/PM EZOLV
OLV/PM
Enables and disables the function to change parameter settings during a Uv [DC Bus Undervoltage]
condition. Use this parameter with 24 V Power Supply option revision B or later.
V/f
OLV/PM
OLV/PM EZOLV
Sets the function to give a warning if the backup external 24 V power supply turns off when the main
circuit power supply is in operation.
V/f
OLV/PM EZOLV
OLV/PM
Sets the function to show the LED status rings and keypad LED lamps.
V/f
OLV/PM EZOLV
OLV/PM
When you connect a backup external 24 V power supply, this parameter sets the function to trigger
an alarm when the main circuit power supply voltage decreases.
Description
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
(Range)
-
Default
(Range)
0
(0, 1)
Default
(Setting Range)
0
(0, 1)
Default
(Range)
2
(0 - 2)
Default
(Range)
1
(0, 1)