YASKAWA HV600 Manual page 290

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.8 H: Terminal Functions
• Fully stop the motor
• Cancel the Run command
• Cancel the fast stop command
Note:
• To use the N.O. switch to input the fast stop command, set 15 (Fast Stop (N.O.)).
• Refer to
C1-09: Fast Stop Time on page 224
• Set C1-09 [Fast Stop Time] to a correct deceleration time. If the deceleration time is too short, it can cause an overvoltage fault and failure
to stop the motor from coasting.
Figure 2.52
shows an example of how fast stop operates.
C1-09:
18: Timer Function
Setting Value
Function
18
Timer Function
Note:
Refer to "b4: Timer Function" for more information.
19: PID Disable
Setting Value
Function
19
PID Disable
ON : PID control disabled
OFF : PID control enabled
1B: Programming Lockout
Setting Value
Function
1B
Programming Lockout
You can continue to view parameter setting values when the terminal is OFF [Parameters Cannot be Edited].
ON : Program Lockout
OFF : Parameter Write Prohibit
1E: Reference Sample Hold
Setting Value
Function
1E
Reference Sample Hold
290
for more information.
Figure 2.52 Fast Stop Time Chart
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 12].
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to disable PID control when b5-01 = 1 or 3 [PID Mode Setting = Standard or Fref + PID Trim].
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to prevent parameter changes when the terminal is OFF.
V/f
OLV/PM EZOLV
OLV/PM
Sets the command to sample the frequency reference at terminals A1 or A2 and hold the frequency reference at that frequency.
Description
Description
Description
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming