YASKAWA HV600 Manual page 131

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
UC-11
# of BN COV Sbscrpt
(3DBA)
UC-12
MSTP Loop TIme
(3DBB)
UC-13
BN MSTP CRC Errors
(3DBC)
UC-14
BN MSTP Tokens Lost
(3DBD)
UC-15
BN MSTP Tokens Retry
(3DBE)
UC-16
BN MSTP Silence Avg
(3DBF)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
Shows the number of COV subscriptions requested by the nodes on the BACnet network. This is
limited to the number of objects that support COV subscriptions.
Unit: 1
V/f
OLV/PM EZOLV
OLV/PM
Shows the number of milliseconds between drive transmitted token and drive token received,
showing how long the MSTP loop took to pass the token to all nodes on the MSTP network.
Unit: 1 ms
V/f
OLV/PM
OLV/PM EZOLV
Shows the number of CRC errors detected after you energize the drive.
Unit: 1
V/f
OLV/PM
OLV/PM EZOLV
Shows the number of token losses seen by the unit since power-on. This is sensed by a net deadtime
of greater than 500 ms.
Unit: 1
V/f
OLV/PM EZOLV
OLV/PM
Shows the number of token retries seen by the unit since power-on. This is sensed by two subsequent
token frames seen from the same node to the same node with the same CRC.
Unit: 1
V/f
OLV/PM EZOLV
OLV/PM
Shows the average net deadtime (space between active messages), averaged over a 60 packet period.
Unit: 1.0 ms
Description
1.18 U: Monitors
MFAO Signal Level
No Signal output available
No signal output available
No signal output available
No signal output available
No signal output available
No signal output available
1
131

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents