YF-10
PI Aux Low Level
Detection Time
(3F59)
RUN
YF-11
PI Aux Control Low
Level Det Sel
(3F5A)
YF-12
PI Aux Control High
Level Detect
(3F5B)
RUN
YF-13
PI Aux High Level
Detection Time
(3F5C)
RUN
YF-14
PI Aux Control Hi Level
Det Sel
(3F5D)
YF-15
PI Aux Level Detect
Restart Time
(3F5E)
YF-16
PI Auxiliary Control P
Gain
(3F5F)
RUN
YF-17
PI Auxiliary Control I
Time
(3F60)
RUN
YF-18
PI Aux Control Detect
Time Unit
(3F61)
YF-19
PI Aux Ctrl Feedback
WireBreak
(3F62)
YF-20
PI Aux Main PI Speed
Control
(3F63)
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Description
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time that the PI Aux Feedback must be less than YF-09 [PI Aux Control
Low Lvl Detection] to trigger a drive response when YF-11 = 2 and 3 [PI Aux Control Low
Level Det Sel = Fault and Auto-Restart (time set by YF-15)].
V/f
OLV/PM
OLV/PM EZOLV
Sets drive response when the PI Aux Feedback decreases to less than YF-09 [PI Aux
Control Low Lvl Detection] for longer than YF-10 [PI Aux Control Low Lvl Det Time].
0 : No Display
1 : Alarm Only
2 : Fault
3 : Auto-Restart (time set by YF-15)
Note:
• Set YF-01 = 1 [PI Aux Control Selection = Enabled] and YF-09 [PI Aux Control
Low Level Detect] > 0 to enable PI Aux Low Level Detection.
• Parameter YF-10 only applies when YF-11 = 2 or 3.
V/f
OLV/PM
OLV/PM EZOLV
Sets the value above which the level must be for longer than YF-13 [PI Aux High Level
Detection Time] to respond as specified by YF-14 [PI Aux Hi Level Detection Select].
Note:
• Set this parameter to 0.0 to disable the function.
• Parameter YF-13 only applies to when YF-14 = 2 and 3 [Fault and Auto-Restart
(time set by YF-15)].
• Parameters YF-21 [PI Aux Ctrl Level Unit Selection] and YF-22 [PI Aux Level
Decimal Place Pos] set the unit and resolution.
V/f
OLV/PM EZOLV
OLV/PM
Sets the length of time that the level must be more than YF-12 [PI Aux Control High Level
Detect] before the drive will respond when YF-14 = 2, 3 [PI Aux Hi Level Detection
Select].
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive response when the PI Aux Feedback increases to more than the YF-12 [PI
Aux Control High Level Detect] level for longer than the time set in YF-13 [PI Aux High
Level Detection Time].
0 : NoDisplay (Digital Output Only)
1 : Alarm Only
2 : Fault
3 : Auto-Restart (time set by YF-15)
Note:
• Set YF-01 = 1 [PI Aux Control Selection = Enabled] and YF-12 [PI Aux Control
High Level Detect] > 0 to enable PI Aux High Level Detection.
• Parameter YF-13 only applies when YF-14 = 2 or 3
V/f
OLV/PM
OLV/PM EZOLV
Sets the length of time the drive will wait before it tries an Auto-Restart of LOAUX [Low
PI Aux Feedback Level] or HIAUX [High PI Aux Feedback Level] fault.
V/f
OLV/PM EZOLV
OLV/PM
Sets the proportional gain for the suction pressure control.
V/f
OLV/PM
OLV/PM EZOLV
Sets the integral time for the suction pressure control.
Note:
Set this parameter to 0.0 to disable the integrator.
V/f
OLV/PM
OLV/PM EZOLV
Sets the time unit for YF-10 [PI Aux Control Low Lvl Det Time] and YF-13 [PI Aux High
Level Detection Time].
0 : Minutes (min)
1 : Seconds (sec)
V/f
OLV/PM EZOLV
OLV/PM
Sets how the analog input selected for PI Aux Feedback will respond when it is
programmed to receive a 4 mA to 20 mA signal and the signal is lost.
0 : Disabled
1 : Alarm Only
2 : Fault (no retry, coast to stop)
V/f
OLV/PM EZOLV
OLV/PM
Sets if the PI Auxiliary Controller has an effect on output speed.
0 : Disabled
1 : Enabled
1.19 Y: Application Features
Default
Ref.
(Range)
0.1 s
500
(0.0 - 300.0 s)
1
500
(0 - 3)
0.0 PSI
501
(-999.9 - +999.9 PSI)
0.1 s
501
(0.0 - 300.0 s)
1
501
(0 - 3)
5.0 min
502
(0.1 - 6000.0 min)
2.00
502
(0.00 - 25.00)
5.0 s
502
(0.0 - 360.0 s)
1
502
(0, 1)
2
502
(0 - 2)
1
502
(0, 1)
1
143