E: Motor Parameters; E1: V/F Pattern For Motor 1 - YASKAWA HV600 Manual

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

1.8 E: Motor Parameters

1.8

E: Motor Parameters

E1: V/f Pattern for Motor 1

No.
Name
(Hex.)
E1-01
Input AC Supply Voltage
(0300)
E1-03
V/f Pattern Selection
(0302)
E1-04
Maximum Output
Frequency
(0303)
E1-05
Maximum Output Voltage
(0304)
E1-06
Base Frequency
(0305)
E1-07
Mid Point A Frequency
(0306)
E1-08
Mid Point A Voltage
(0307)
E1-09
Minimum Output
Frequency
(0308)
E1-10
Minimum Output Voltage
(0309)
42
V/f
OLV/PM EZOLV
OLV/PM
Sets the drive input voltage.
NOTICE: Set parameter E1-01 to align with the drive input
voltage (not motor voltage). If this parameter is incorrect, the
protective functions of the drive will not operate correctly and it
can cause damage to the drive.
V/f
OLV/PM
OLV/PM EZOLV
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you
can make a custom pattern.
0 : Const Trq, 50Hz base, 50Hz max
1 : Const Trq, 60Hz base, 60Hz max
2 : Const Trq, 50Hz base, 60Hz max
3 : Const Trq, 60Hz base, 72Hz max
4 : VT, 50Hz, 65% Vmid reduction
5 : VT, 50Hz, 50% Vmid reduction
6 : VT, 60 Hz, 65% Vmid reduction
7 : VT, 60Hz, 50% Vmid reduction
8 : High Trq, 50Hz, 25% Vmin boost
9 : High Trq, 50Hz, 65% Vmin boost
A : High Trq, 60Hz, 25% Vmin boost
B : High Trq, 60Hz, 65% Vmin boost
C : High Freq, 60Hz base, 90Hz max
D : High Freq, 60Hz base, 120Hz max
E : High Freq, 60Hz base, 180Hz max
F : Custom
Note:
• Set the correct V/f pattern for the application and operation area. An incorrect V/f
pattern can decrease motor torque and increase current from overexcitation.
• Parameter A1-03 [Initialize Parameters] will not initialize the value of E1-03.
V/f
OLV/PM EZOLV
OLV/PM
Sets the maximum output frequency for the V/f pattern.
V/f
OLV/PM
OLV/PM EZOLV
Sets the maximum output voltage for the V/f pattern.
V/f
OLV/PM EZOLV
OLV/PM
Sets the base frequency for the V/f pattern.
V/f
OLV/PM
OLV/PM EZOLV
Sets a middle output frequency for the V/f pattern.
V/f
OLV/PM
OLV/PM EZOLV
Sets a middle output voltage for the V/f pattern.
V/f
OLV/PM EZOLV
OLV/PM
Sets the minimum output frequency for the V/f pattern.
V/f
OLV/PM EZOLV
OLV/PM
Sets the minimum output voltage for the V/f pattern.
Description
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
Default
Ref.
(Range)
208 V Class: 240 V,
246
480 V Class: 480 V
(208 V Class: 155 - 255
V,
480 V Class: 310 - 510
V)
F
246
(Determined by A1-02)
Determined by A1-02 and
251
E5-01
(Determined by A1-02
and E5-01)
208 V Class: 230.0 V,
251
480 V Class: 460.0 V
(208 V Class: 0.0 - 255.0
V,
480 V Class: 0.0 - 510.0
V)
Determined by A1-02 and
251
E5-01
(0.0 - E1-04)
Determined by A1-02
252
(0.0 - E1-04)
Determined by A1-02 and
252
o2-04
(208 V Class: 0.0 - 255.0
V,
480 V Class: 0.0 - 510.0
V)
Determined by A1-02 and
252
E5-01
(Determined by A1-02,
E1-04, and E5-01)
Determined by A1-02
252
(208 V Class: 0.0 - 255.0
V,
480 V Class: 0.0 - 510.0
V)