Setting Value
Function
11E
!Executing Auto-Restart
11F
!Motor Overload Alarm
(oL1)
120
!Drive Overheat Pre-
Alarm (oH)
121
!Safe Torque OFF
12F
!Maintenance
Notification
130
!During Torque Limit
137
!During Frequency
Output
138
!Drive Enabled
139
!Watt Hour Pulse Output
13A
!Drive Overheat Alarm
13D
!During Speed Search
142
!Pressure Reached
14A
!During KEB Ride-Thru
14B
!During Short Circuit
Braking
14C
!During Fast Stop
14D
!oH Pre-Alarm Reduction
Limit
151
!Sequence Timer 1
152
!Sequence Timer 2
153
!Sequence Timer 3
154
!Sequence Timer 4
158
!UL6 Underload Detected
YASKAWA TOEPYAIHV6002A HV600 Drive Programming
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the Auto Restart function is trying to restart after a fault.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive heatsink temperature is at the level set with L8-02 [Overheat Alarm Level].
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly
and when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety circuit fault or RUN/READY
OFF : Safety stop state
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
• IGBT
• Cooling fan
• Capacitor
• Soft charge bypass relay
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the torque reference is the torque limit set with L7 parameters, H3-02, or H3-10 [MFAI
Function Selection].
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive outputs frequency.
ON : The drive does not output frequency.
OFF : The drive outputs frequency.
V/f
OLV/PM
OLV/PM EZOLV
This terminal deactivates when the H1-xx = 6A [Drive Enable] terminal deactivates.
V/f
OLV/PM
OLV/PM EZOLV
Outputs the pulse that shows the watt hours.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive heatsink temperature is at the L8-02 [Overheat Alarm Level] setting while L8-
03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and the drive is running.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive is doing speed search.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when the drive is at the Pressure Setpoint.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates during KEB Ride-Thru.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates during Short Circuit Braking.
Note:
When A1-02 = 8 [Control Method Selection = EZOLV], this function is available only when you use a PM motor.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the fast stop is in operation.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)] and
oH [Heatsink Overheat] does not clear after the drive decreases the frequency for 10 cycles.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when Sequence Timer 1 is active.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when Sequence Timer 2 is active.
V/f
OLV/PM EZOLV
OLV/PM
The terminal deactivates when Sequence Timer 3 is active.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when Sequence Timer 4 is active.
V/f
OLV/PM
OLV/PM EZOLV
The terminal deactivates when the drive detected UL6 [Underload or Belt Break Detected].