• Yaskawa can change the products, specifications, and content of the instructions without notice to make the product and/or the instructions better. • If you damage or lose these instructions, contact a Yaskawa representative or the nearest Yaskawa sales office on the rear cover of the manual, and tell them the document number on the front cover to order new copies.
Popular building automation communication protocols BACnet, Siemens APOGEE, Johnson Controls Metasys and MEMOBUS/Modbus are embedded in the drive. Interface cards for LonWorks, Ethernet/IP, EtherNet/IP (DLR), Modbus TCP/IP (Dual-Port and Single-Port), and Multi-protocol EtherNet are offered separately. YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL...
• Verify receipt of the correct model by checking the catalog code printed on the nameplate of the package. • Contact your supplier if you have received the wrong model or the package does not function properly. YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL...
Page 8
TECH: DATE SIZE REVI SION PAGE (T1) (T2) (T3) APPROVED: M.KOEHLER DATE 06/16/15 DRAWING #: A.C. MOTOR ORIGINAL DESIGN: M.KOEHLER DATE 06/15/15 DS.Z1R1.02 Prepared by don_tumilson 10/26/2015 7:31:04 AM ◆ System Components YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL...
Page 9
Copy Allowed Selection = Enabled S5-01 – HAND Frequency Reference Selection = S5-05 S5-04 – HAND-OFF-AUTO Behavior = Normal S5-05 HAND Frequency Reference 1 S5-07 – HAND Key Function Selection = Disabled YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL...
480VAC 3PH 60HZ A.C. LINES to 202 NOTE 1 GROUND EARTH Verify that the parameters in Drive A and Drive B are set to Yaskawa factory default values. Refer to CONT ROL BOARD CONT ROL BOARD DOOR MO UNTED DIGITA L OPERATOR...
Confirm that you can use the BAS to start and stop Drive A and Drive B in AUTO. □ Confirm that you can use the BAS to change the speed reference for Drive A and Drive B. YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL...
When you jumper terminal SN to S3, Drive A will fault on an EF3 fault code. Confirm that the corresponding drive fault relay output is in a faulted state. Drive B will then attempt to start immediately. Confirm Drive B starts operating. YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL...
Revision History Date of Publication Revision Number Revised Content April 2023 <2> Revision: Applicable Documents and Catalog Code February 2023 <1> Revision: Document title Addition: Factory Set Parameters August 2022 First release YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL...
Page 14
2121, Norman Drive South, Waukegan, IL Philipp-Reis-Str. 6, 65795 Hattersheim am LTDA. 60085, U.S.A. Main, Germany 777, Avenida Piraporinha, Diadema, São Phone: +1-800-YASKAWA (927-5292) or +1- Phone: +49-6196-569-300 Fax: +49-6196- Paulo, 09950-000, Brasil 847-887-7000 Fax: +1-847-887-7310 569-398 Phone: +55-11-3585-1100 Fax: +55-11-3585- www.yaskawa.com...