Page 1
YASKAWA AC Drive Option LonWorks Installation Manual Type: SI-W3 To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual. 安川インバータ オプション LonWorks 通信 取扱説明書 形 式 SI-W3 製品を安全にお使いいただくために,この取扱説明書を必ずお読みください。...
Page 2
Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice.
Any warnings provided by YASKAWA must be promptly provided to the end user. YASKAWA offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED.
Page 5
• LED Keypad for YASKAWA AC Drive GA700 and GA800 Registered Trademarks • LonWorks is a trademark of ECHELON USA. • Trademarks are the property of their respective owners. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 6
Indicates a hazardous situation, which, if not avoided, could cause death or serious injury. CAUTION Indicates a hazardous situation, which, if not avoided, could cause minor or moderate injury. NOTICE Indicates an equipment damage message. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 7
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual. • Contact Yaskawa or a Yaskawa representative and provide the manual number shown on the front cover to order new copies of the manual.
Page 8
Failure to comply could result in damage to the drive or option and will void warranty. Yaskawa is not responsible for any modification of the product made by the user. Do not expose the drive or the option to halogen group disinfectants. Do not pack the drive or the option in fumigated or sterilized wooden materials.
1, refer to the web page below to confirm this manual is correct for your product. The web page provides a list of option manuals by product, and a direct link to download a PDF. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 10
2 Overview Scan QR code Or refer to: http://www.yaskawa.com/optionlookup YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Refer to Figure 1 on page for details. Contact the distributor where the option was purchased or contact Yaskawa or a Yaskawa representative about any problems with the option. Option Package Contents LED Labels Ground...
Z1000U product series do not support this connector and associated DDC functions. <3> Connect the provided ground wire during installation. Installation on GA700 and GA800 drives does not require the ground wire. Figure 1 Option Components YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 13
DANGER! Electric Shock Hazard. Do not touch drive main terminals and control terminals. Failure to comply will result in death or serious injury. Connect an LED operator for YASKAWA AC Drive 1000-Series (model: JVOP-182) to connector CN3 using an RJ-45 cable (RJ-45 8-pin straight connection) to set Direct Digital Control (DDC) function parameters.
Page 14
If the unit does not recover after cycling power, then the option card may need to be replaced. Receiving Receiving node data Flashing Green Node data not yet No input signal received YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 15
LonWorks network has not been configured Option operating The option is operating normally. Note: The RUN, RX, TX, and ERR LEDs are lit (ON) during initialization of the bind data. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Do not remove covers or touch circuit boards while the drive is energized. Failure to comply could cause death or serious injury. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 17
Failure to comply could prevent proper operation and damage equipment. Confirm that all connections are correct after installing the option and connecting peripheral devices. Failure to comply could damage the option. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 18
Procedures for Installing and Product Series Page Wiring Options on a Drive A1000 Procedure A U1000 Procedure A Z1000 Procedure B Z1000U Procedure B GA700 Procedure C GA800 Procedure C YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 19
G – Removable tabs for wire routing N – Connector CN5-C (Not available for communication H – Included screws option installation.) I – Ground wire Figure 3 Drive Components with Option YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 20
NOTICE: Damage to Equipment. Observe proper electrostatic discharge (ESD) procedures when handling the option, drive, and circuit boards. Failure to comply could cause ESD damage to circuitry. Figure 4 Figure 4 Remove the Keypad, Front Cover, and Terminal Cover YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 21
(B) into the CN5-A (L) connector on the drive and fasten it into place using one of the included screws (H). Figure 6 Figure 6 Insert the Option YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 22
Figure 7 Connect the Ground Wire Note: The drive has only two ground terminal screw holes (I). Two ground wires should share the same ground terminal when connecting three options. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 23
Install LonWorks communications cables apart from main-circuit wiring and other electrical and power lines. Ensure the cable end is firmly connected (see Figure 22). Refer to Communication Cable Topology on page 38 for details of installing. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 24
NOTICE: Do not pinch cables between the front covers and the drive. Failure to comply could cause erroneous operation. Figure 9 Figure 9 Replace the Front Covers and Keypad Set drive parameters in Table 5 for correct option performance. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 25
H – Terminal block CN1 D – Drive front cover I – Insert connector CN5 here E – HOA keypad J – Connector CN5 Figure 10 Drive Components with Option YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 26
NOTICE: Damage to Equipment. Observe proper electrostatic discharge (ESD) procedures when handling the option, drive, and circuit boards. Failure to comply could cause ESD damage to circuitry. Figure 11 Figure 11 Remove the HOA Keypad and Front Cover YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 27
5 Installation Procedure Affix the LED label (F) in the appropriate position on the drive front cover (D). Figure 12 Figure 12 Affix the LED Label YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 28
(B) into the CN5-A (J) connector on the drive and fasten it into place using one of the included screws (C). Figure 13 Figure 13 Insert the Option YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 29
Install LonWorks communications cables apart from main-circuit wiring and other electrical and power lines. Ensure the cable end is firmly connected (see Figure 22). Refer to Communication Cable Topology on page 38 for details of installing. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 30
NOTICE: Do not pinch cables between the front covers and the drive. Failure to comply could cause erroneous operation. Figure 15 Figure 15 Replace the Front Cover and HOA Keypad Set drive parameters in Table 5 for correct option performance. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 31
K – Connector CN5-C (Not available for communication F – Keypad option installation.) G – Terminal block CN1 H – LED Status Ring board Figure 16 Drive Components with Option YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 32
You can only install this option into the CN5-A connector on the drive control board. Affix the LED label (E) in the appropriate position on the drive front cover (D). Figure 17 Figure 17 Affix the LED Label YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 33
Insert the keypad connector tab into the holder when installing the keypad connector to the holder. Holder Keypad connector tab Keypad connector Figure 18 Remove the Front Cover and Keypad YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 34
NOTICE: Do not remove the LED Status Ring board cable connector. Failure to comply could cause erroneous operation and damage the drive. Figure 19 Temporary placement holes Drive front view Figure 19 Remove the LED Status Ring Board YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 35
Use the open space provided inside the LED Status Ring board to route option wiring. NOTICE: Do not pinch cables between the front cover or the LED Status Ring board and the drive. Failure to comply could cause erroneous operation. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 36
At that time, insert the keypad connector tab into the drive. Keypad connector Figure 21 Replace the Front Cover and Keypad Set drive parameters in Table 5 for correct option performance. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 37
Filter Install Location Filter Type Series/Part Number Main circuit (input) EMI/RFI Filter LNFD series Main circuit (output to motor) Zero Phase Reactor F6054GB, F11080GB, F200160PB YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 38
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not come into contact with other wiring. Insufficient insulation may cause a short circuit that can damage the option or the drive. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 39
XIF files and the resource files for this option card can be obtained from: U.S.: http://www.yaskawa.com Europe: http://www.yaskawa.eu.com Japan: http://www.e-mechatronics.com Other areas: Check the back cover of these manuals. For questions, contact Yaskawa or a Yaskawa representative. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 41
<5> The setting specifies that network communications provide the torque reference or torque limit. The motor may not rotate if the PLC does not supply a torque reference or torque limit. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 45
26 out_of_service Not supported. (Always 0) bit 25 mechanical_fault Not supported. (Always 0) bit 24 feedback_failure Not supported. (Always 0) bit 23 over_range Not supported. (Always 0) YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
The option is not properly connected Reinstall the option to the drive If there are no problems with the wiring and the error continues to occur, Option is damaged replace the option. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 50
The option card connection to port 2. Check if the option is properly plugged into the option port. CN5-A is faulty. 3. Replace the option if the fault continues to occur. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 51
Option Flash write mode. Cause Possible Solution An option of the same type is already installed in option port CN5-A, Connect the option to the correct option port. CN5-B, or CN5-C. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 52
Note: If the option software version is not compatible or if update the communication option you install an incorrect option to the drive, it will trigger an parameters. alarm. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 53
<3> Not available with 1000-Series drive models with a capacities between 450 and 630 kW. <4> When you use the input status of AI-A3 and DI-A3 as a monitor, you can connect AI-A3 and DI-A3 to CN5-A, CN5-B, or CN5-C. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
EMC guidelines: Use dedicated shield cable for the option and external device (encoder, I/O device, master), or run the wiring through a metal conduit. YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 55
Cable clamp I/O option I/O device CN5-A, CN5-B, CN5-C Cable clamp Communication Master option CN5-A Figure 29 Option Installation for CE Compliance (PG-, DI-, DO-, AI-, AO-, SI-) YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
• Radioactive materials or flammable materials, including wood Area of Use • Harmful gas or fluids • Salt • Direct sunlight • Falling foreign objects Altitude 1000 m (3280 ft) or lower YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 57
Revision: Reviewed and corrected entire documentation. Back cover Revision: Address July 2017 <1> Chapter 2 Addition: Note in Table 1 Back cover Revision: Address December 2016 – – First edition YASKAWA ELECTRIC TOBP C730600 93C YASKAWA AC Drive Option SI-W3 Installation Manual...
Page 58
Phone: +81-3-5402-4502 Fax: +81-3-5402-4580 http://www.yaskawa.co.jp YASKAWA AMERICA, INC. 2121, Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: +1-800-YASKAWA (927-5292) or +1-847-887-7000 Fax: +1-847-887-7310 http://www.yaskawa.com YASKAWA ELÉTRICO DO BRASIL LTDA. 777, Avenida Piraporinha, Diadema, São Paulo, 09950-000, Brasil Phone: +55-11-3585-1100 Fax: +55-11-3585-1187 http://www.yaskawa.com.br...
Need help?
Do you have a question about the LonWorks SI-W3 and is the answer not in the manual?
Questions and answers