Dlp- A322 Manual Or Force Switch The Node Timing Reference - Cisco ONS 15454 Series Procedure Manual

Hide thumbs Also See for ONS 15454 Series:
Table of Contents

Advertisement

Chapter 20
DLPs A300 to A399
DLP-A322 Manual or Force Switch the Node Timing Reference
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
In node view, click the Maintenance > Timing > Source tabs.
Step 1
From the Reference drop-down list for the desired Clock, choose the desired reference.
Step 2
From the Operation drop-down list for the desired Clock, choose one of the following options:
Step 3
Click Apply next to the timing source.
Step 4
Click Yes in the confirmation dialog box. If the selected timing reference is an acceptable valid
Step 5
reference, the node switches to the selected timing reference.
If the selected timing reference is invalid, a warning dialog box appears. Click OK; the node does not
Step 6
revert to the normal timing reference.
Return to your originating procedure (NTP).
Step 7
DLP-A323 Clear a Manual or Force Switch on a Node Timing Reference
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
In node view, click the Maintenance > Timing > Source tabs.
Step 1
March 2005
Manual—This operation commands the node to switch to the reference you have selected if the
SSM quality of the reference is not lower than the current timing reference.
Force—This operation commands the node to switch to the reference you have selected, regardless
of the SSM quality (if the reference is valid).
For information about the Clear option, see the
Node Timing Reference" task on page
DLP-A322 Manual or Force Switch the Node Timing Reference
This task commands the node to switch to the timing reference you have
selected A Manual switch switches the reference if the synchronization
status message (SSM) quality of the requested reference is not less than
the current reference. A Force switch switches the reference regardless
of SSM quality.
None
DLP-A60 Log into CTC, page 17-66
As needed
Onsite or remote
Maintenance or higher
"DLP-A323 Clear a Manual or Force Switch on a
20-13.
This task clears a Manual or Force switch on a node timing reference and
reverts the timing reference to its provisioned reference.
None
DLP-A60 Log into CTC, page 17-66
As needed
Onsite or remote
Maintenance or higher
Cisco ONS 15454 Procedure Guide, R5.0
20-13