To remove the transient messages from the History window, click Delete Cleared Alarms. Transient
Step 5
messages are single messages, not raise-and-clear pairs (that is, they do not have companion messages
stating they are cleared).
Stop. You have completed this procedure.
NTP-A69 View Alarm-Affected Circuits
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Complete the
Step 1
Step
In the network, node, or card view, click the Alarms tab or Conditions tab and then right-click anywhere
Step 2
in the row of an active alarm or condition.
Note
The Select Affected Circuit option appears on the shortcut menu
Cisco ONS 15454 Procedure Guide, R5.0
7-4
Use this procedure to view all circuits, if any, that are affected by an alarm
or condition.
None
NTP-A196 View Alarms, History, Events, and Conditions, page 7-2
As needed
Onsite or remote
Retrieve or higher
"DLP-A60 Log into CTC" task on page
2.
The node view is the default, but you can also navigate to the Alarms tab in the network view or
card view to perform Step 2.
Chapter 7
17-66. If you are already logged in, continue with

(Figure

7-1).
Manage Alarms