DLP-A6 Mount the Shelf Assembly in a Rack (Two People)
Ensure that the shelf assembly is set for the desired rack size (either 23 inches [584.2 mm] or 19 inches
Step 2
[482.6 mm]).
Using the hex tool that shipped with the assembly, install the two set screws into the screw holes that
Step 3
will not be used to mount the shelf. Let the screws protrude sufficiently to hold the mounting bracket.
Lift the shelf assembly to the desired rack position and set it on the set screws.
Step 4
Align the screw holes on the mounting bracket with the mounting holes in the rack.
Step 5
Using the Phillips screwdriver, install one mounting screw in each side of the assembly.
Step 6
When the shelf assembly is secured to the rack, install the remaining mounting screws.
Step 7
Note
Step 8
Using the hex tool, remove the temporary set screws.
Step 9
Return to your originating procedure (NTP).
DLP-A6 Mount the Shelf Assembly in a Rack (Two People)
Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Verify that the proper fuse and alarm panel has been installed in the top mounting space. If a fuse and
Step 1
alarm panel is not present, you must install one according to the manufacturer's instructions.
Ensure that the shelf assembly is set for the desired rack size (either 23 inches [584.2 mm] or 19 inches
Step 2
[482.6 mm]).
Using the hex tool that shipped with the shelf assembly, install the two set screws (48-1003-XX) into the
Step 3
screw holes that will not be used to mount the shelf. Let the set screws protrude sufficiently to hold the
mounting brackets.
Cisco ONS 15454 Procedure Guide, R5.0
17-6
Use at least one set of the horizontal screw slots on the ONS 15454 to prevent slippage.
This task allows two people to mount the shelf assembly in a rack.
Pinned hex tool
Two set screws (48-1003-XX)
Eight pan-head Phillips mounting screws (48-1004-XX, 48-1007-XX)
#2 Phillips screwdriver
DLP-A3 Reverse the Mounting Bracket to Fit a 19-inch (482.6 mm) Rack,
page
DLP-A4 Install the External Brackets and Air Filter, page
applicable
Required
Onsite
None
If you are installing the 15454-SA-ANSI or 15454-SA-HD shelf assembly, a 100-A fuse panel
(30-A fuse per shelf minimum) is required.
If you are installing the 15454-SA-NEBS3 shelf assembly, a standard 80-A fuse panel (20-A fuse
per shelf minimum) is required.
17-2, if applicable
Chapter 17
DLPs A1 to A99
17-4, if
March 2005