Code
Name
oFA01
Option Card Fault (CN5-A)
oFA03, oFA04
Option Card Error (CN5-A)
oFA30 to
Option Card Connection Error
oFA43
(CN5-A)
oFb00
Option Not Compatible with Port
oFb02
Option Fault
oFC00
Option Fault (CN5-B)
oFC02
Option Fault
PSE
JOHB-SMP3 Protocol Set Error

Minor Faults and Alarms

Code
Name
PA1
PLC Alarm 1

bUS Fault Tolerance

bUS Fault Auto-Restart

Parameter F6-14 [bUS Fault Auto Reset Select] will appear when the option is installed.
Setting F6-14 = 0 [Disabled] or F6-01 = 3, 4, 5 [Alarm Only, Alarm (Run at d1-04), Alarm - Ramp Stop] will not
affect standard default drive behavior.
Setting F6-14 = 1 [Enabled] AND F6-01 ≤ 2 [Fast Stop (Use C1-09)] will cause the following operation:
1. The bUS fault occurs after the time set in F7-57 [BACnet/IP bUS Timeout Value].
2. When the condition is removed, the option commands a fault reset and returns control of the drive to the
BACnet/IP network.
Note:
A change of F6-14 does not require a power cycle or parameter reload.
When F7-57 > 0 [BACnet/IP BUS Timeout Value > 0 seconds], the BACnet/IP controller must periodically send a
Frequency Reference Command (AV2), or a Run/Stop command (AV1, BV1, BV2, BV58, BV59 and AV43 to
AV51 where supported). If the BACnet/IP controller does not send a command for the length of time set in F7-57
and the drive is running, the drive will detect a bUS [Option Communication Error] fault.
To disable BACnet/IP Timeout detection, set F7-57 = 0. When this parameter is set to 0, a periodic command
from the BACnet/IP controller is not necessary.
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Causes
BACnet/IP is not installed on the JOHB-SMP3
card.
Drive software is not compatible with BACnet/IP
on the JOHB-SMP3 card.
The option connected to the option port CN5-A was
changed during run.
A fault occurred in the option.
A fault occurred in the option.
The option connected to connector CN5-B is not
compatible.
An option of the same type is already installed in
the option port CN5-A, CN5-B, or CN5-C.
The option connected to connector CN5-C is not
compatible.
An option of the same type is already installed in
the option port CN5-A, CN5-B, or CN5-C.
Invalid DIP switch S1 setting.
BACnet/IP is not installed on the JOHB-SMP3
card.
Causes
Port 1 is at a link speed different from Port 2 (100
Mbps and 10 Mbps). Data will not be passed
between the two ports in this condition.
9 Troubleshooting
Possible Solutions
Upgrade the software in the JOHB-SMP3. For details, consult
your local Yaskawa representative.
Upgrade the software in the drive. For details, consult your local
Yaskawa representative.
1.
De-energize the drive.
2.
Connect the option to the correct option port.
1.
De-energize the drive.
2.
Make sure that the option is correctly connected to the
connector.
3.
If the problem continues, replace the option.
1.
De-energize the drive.
2.
Make sure that the option is correctly connected to the
connector.
3.
If the problem continues, replace the option.
Connect the option to the correct connector.
• Use connector CN5-A when you connect the option.
To use other options, refer to those option manuals.
Connect the option to the correct connector.
Connect the option to the correct connector.
• Use connector CN5-A when you connect the option.
To use other options, refer to those option manuals.
Connect the option to the correct option port.
Set the option DIP switch S1 as shown in page 11. Monitor, U4-
75 [Communication OPT Protocol] will display the DIP switch
S1 setting.
Upgrade the software in the JOHB-SMP3. For details, consult
your local Yaskawa representative.
Possible Solutions
• AUTO NEGOTIATE: When F7-14 = 1 [Duplex Mode
Selection = Auto/Auto (Auto Negotiation/Auto Negotiation)],
make sure that the devices connected to the two ports of the
JOHB-SMP3 have the same speed (both at 10 Mbps or both at
100 Mbps).
• FORCED DUPLEX SETTING: When F7-14 ≠1 [Duplex
Mode Selection ≠ Auto/Auto (Auto Negotiation/Auto
Negotiation)], set the two connected ports to the same speed
using F7-15. You cannot set F7-15 to 101 or 102.