Page 1
YASKAWA AC Drive J1000 Compact V/f Control Drive Quick Start Guide Type: CIMR-JC Models: 200 V Class, Three-Phase Input: 0.1 to 5.5 kW 200 V Class, Single-Phase Input: 0.1 to 2.2 kW 400 V Class, Three-Phase Input: 0.2 to 5.5 kW To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance.
Page 2
YASKAWA. No patent lia- bility is assumed with respect to the use of the information contained herein. Moreover, because YASKAWA is constantly striving to improve its high-quality products, the informa- tion contained in this manual is subject to change without notice.
1 Safety Instructions and General Warnings Safety Instructions and General Warnings YASKAWA Electric supplies component parts for use in a wide variety of industrial applica- tions. The selection and application of YASKAWA products remain the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its prod- ucts are incorporated into the final system design.
Page 5
• Do not attempt to modify or alter the drive in any way not explained in this manual. Failure to comply could result in death or serious injury. YASKAWA is not responsible for any modification of the product made by the user. This product must not be modified.
Page 6
• Do not carry the drive by the front cover. Failure to comply may result in minor or moderate injury from the main body of the drive falling. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 6...
Page 7
• Do not modify the drive circuitry. Failure to comply could result in damage to the drive and will void warranty. YASKAWA is not responsible for modification of the product made by the user. This product must not be modified.
Page 8
Ground the neutral point of the main power supply for 400 V Class drives. Precautions for UL/cUL Standards Compliance This drive is tested in accordance with UL standard UL508C and complies with UL require- ments. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 8...
10 - 20 Hz at 9.8 m/s , 20 - 55 Hz at 5.9 m/s Orientation Install the drive vertically to maintain maximum cooling effects. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 9...
(default setting) (Output frequency) Analog input Symbols: Indicates a main circuit terminal Use twisted pair cables Use shielded twisted pair cables Indicates a control circuit terminal. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 11...
Page 13
Three-Phase 400 V Class 4A0001 A6T3 FWH-40B 4A0002 A6T6 FWH-40B 4A0004 A6T15 FWH-50B 4A0005 A6T20 FWH-70B 4A0007 A6T25 FWH-70B 4A0009 A6T25 FWH-90B 4A0011 A6T30 FWH-90B YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 13...
Page 14
Ground shield at Ground shield at motor side motor side EMC Standards Compliant Wiring of Single- and Three Phase Units YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 14...
Page 15
(Al). –The power supply must be disconnected automatically in case of discontinuity of the protective earthing conductor. • Keep ground wires as short as possible. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 15...
Page 16
DC power supply input For connecting a DC power supply. For 200 V class: Ground with 100 or less Ground Terminal For 400 V class: Ground with 10 or less (2 terminals) YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 16...
Page 17
250 Vac, 10 mA to 1 A Digital output common Output AM Analog monitor output 0 to 10 Vdc (2 mA or less), Resolution: 1/256 (8 bit) Monitor Output Monitor common YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 17...
On: The output frequency is displayed on the data screen. FOUT FOUT LED Light Off: Anything else than the output frequency is displayed on the data screen. EN 18 YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide...
Page 19
In the Parameter Setting Mode all Parameter Setting Mode drive parameters can be set up. <1> Switching to reverse: The LED is lit when LOCAL is selected YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 19...
Connect the load, run the motor and check the operation Fine tune and set application parameters if necessary. Final check the operation and verify the settings. Drive is ready to run the application EN 20 YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide...
Page 21
If the drive is operated in the REMOTE mode, make sure that the correct sources for the fre- quency reference and Run command are set in parameters b1-01/02 and that the drive is in the REMOTE mode. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 21...
Page 22
Analog input Apply the frequency reference signal to terminal A1. Serial Communica- RS232C or RS422/485 Memobus communication tions Option Potentiometer Option Potentiometer Option YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 22...
Page 23
After taking the steps listed above, the drive should be ready to run the application and per- form the basic functions. For details about more advanced setup refer to the technical man- ual. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 23...
Normal/ Braking Constant torque applications rated current. C6-01 Heavy Duty Current 1:Normal Duty (ND) Selection Variable torque application EN 24 YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide...
Page 25
Motor rated slip in hertz (Hz). Motor Sets the motor overload protection Rated Slip L1-02 Overload time in min. Normally no change is Prot. Time necessary. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 25...
Page 26
U1-10 (terminal S2 enabled) 1: Digital input 3 (terminal S3 enabled) 1: Digital input 4 (terminal S4 enabled) 1: Digital input 5 (terminal S5 enabled) YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 26...
Overcurrent • The accel./decel. times are too short. • Wrong motor data or V/f pattern settings. • A magnetic contactor was switched at the output. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 27...
Page 28
Drive capacity and value set to o2-04 do not Correct the value set to o2-04. match. oPE02 Parameters were set outside the allowable setting Set parameters to the proper values. range. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 28...
Page 29
• Correct the values set to b1-01 and b1-02. • b1-02=2 oPE10 • Check the V/f pattern settings. The V/f pattern setting is incorrect. • Refer to the instruction manual for more details. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 29...
Do not install the drive to an area greater than pollution severity 2 (UL standard). Main Circuit Terminal Wiring YASKAWA recommends using UL-listed copper wires (rated at 75 C) and closed-loop con- nectors or CSA-certified ring connectors sized for the selected wire gauge to maintain proper clearances when wiring the drive.
Page 31
30 C. Input Fuse Selection Use the fuses listed up in the table on page 13 when wiring the main circuit. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 31...
Page 32
The operator must enter the rated current of the motor (T1-04) in the menu during auto-tun- ing. If the auto-tuning operation completes successfully (T1-02 = 0), the value entered into T1-04 will automatically write into E2-01. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 32...
Page 33
Setting L1-01 = 2 selects a motor capable of cooling itself over a 10:1 speed range when run- ning at 100% load. The OL1 function derates the motor when it is running at 1/10 or less of its rated speed. YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 33...
Page 34
Time (minutes) Cold Start Hot Start Motor Current (%) (E2-01=100 %) Motor Overload Protection Time YASKAWA Europe TOEP C710606 27A YASKAWA AC Drive - J1000 Quick Start Guide EN 34...
Page 35
Revision History The revision dates and numbers of the revised manuals are given on the bottom of the back cover. MANUAL NO. TOEP C710606 27A Published in Japan June 2009 08-1 Revision number Date of original publication Date of publication Date of Publication Rev.