B2: Dc Injection Braking And Short Circuit Braking; B3: Speed Search - YASKAWA GA500 GA50U Series Programming Manual

Table of Contents

Advertisement

No.
Name
(Hex.)
b1-16
Run Command Selection 2
(01C5)
b1-17
Run Command at Power Up
(01C6)
b1-35
Digital Input Deadband
Time
(1117)
Expert

b2: DC Injection Braking and Short Circuit Braking

No.
Name
(Hex.)
b2-01
DC Injection/Zero
SpeedThreshold
(0189)
b2-02
DC Injection Braking
Current
(018A)
b2-03
DC Inject Braking Time at
Start
(018B)
b2-04
DC Inject Braking Time at
Stop
(018C)
b2-08
Magnetic Flux
Compensation Value
(0190)
b2-12
Short Circuit Brake Time @
Start
(01BA)
b2-13
Short Circuit Brake Time @
Stop
(01BB)
b2-18
Short Circuit Braking
Current
(0177)

b3: Speed Search

No.
Name
(Hex.)
b3-01
Speed Search at Start
Selection
(0191)
b3-02
SpeedSearch Deactivation
Current
(0192)
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the input method for Run Command 2 when the user switches the control circuit terminals ON/
OFF to change the Run command source.
0 : Keypad
1 : Digital Input
2 : Memobus/Modbus Communications
3 : Option PCB
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets drive response when the CPU changes from de-energized to energized and there is an active Run
command. Set this parameter in applications where energizing or de-energizing the drive enables the
Run command. When the CPU stays energized during loss of power, L2-01 [Power Loss Ride
Through Select] sets operation.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the deadband time for MFDIs.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency to start DC Injection Braking or Short Circuit Braking near the end of a stop ramp.
Note:
This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp to Stop].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the DC Injection Braking current as a percentage of the drive rated current.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the DC Injection Braking Time at stop.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the DC Injection Braking Time at stop.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets how much current the drive injects when DC Injection Braking at Start starts (Initial Excitation)
as a percentage of E2-03 [Motor No-Load Current].
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking time at start.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking time at stop.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Short Circuit Braking Current as a percentage of the motor rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor rated current.
• A1-02 = 5, 6 [OLV/PM, AOLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the Speed Search at Start function so the drive will do Speed Search with each Run command.
0 : Disable
1 : Enabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the current level that stops Speed Search as a percentage of the drive rated output current.
Usually it is not necessary to change this setting.
Description
Description
Description
1.5 b: Application
Default
(Setting Range)
0
(0 - 3)
0
(0, 1)
0.0 ms
(0.0 to 100.0 ms)
Default
(Range)
Determined by A1-02
(0.0 - 10.0 Hz)
50%
(0 - 75%)
0.00 s
(0.00 - 10.00 s)
Determined by A1-02
(0.00 - 10.00 s)
0%
(0 - 1000%)
0.00 s
(0.00 - 25.50 s)
A1-02 = 8: 0.00 s
Other than A1-02 = 8: 0.50 s
(0.00 - 25.50 s)
100.0%
(0.0 - 200.0%)
1
Default
(Range)
Determined by A1-02
(0, 1)
Determined by A1-02
(0 - 200%)
23